3.10
Diagnostics
3.10.1
CPU diagnostics
Diagnostics processed by each CPU includes: Diagnostics of comparison between the two CPUs, Software flow
diagnostics, Watchdog, System clock monitor and Detection of a fault not imputable to an identified channel:
o
Power supply diagnostics
o
Temperature diagnostics
o
Comparison diagnostics of redundant channels (1oo2 architecture)
o
CPUs Comparison diagnostic
In case of the above mentioned instances, system switches to safe state.
3.10.2
Analogue inputs diagnostics
The range-ability of the analogue input circuits is from 3 to 21 mA.
CPU’s 1 and 2 perform the following diagnostics:
Under-range
and
Over-range
Both CPU’s assumes that if signal is <3mA or >21mA the transmitter or the acquisition stage is damaged
Action performed:
o
1oo1
architecture:
Valve Control
(SOV energization and closure of actuator)
Local alarm and display of type of fault
Switch-over of Monitor relay
o
1oo2
architecture:
Local “MRT timer” alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in
1oo1
architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or
Valve Control
will be carried out at the end of MRT
time. The menu option
MRT,
in the
Measurement
menu, displays the remaining time before
than MRT time ends
Valve Control
will be carried out if the surviving analogue channel fails in the MRT time
o
1oo3
architecture:
Local “MRT timer” alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in
1oo2
architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or
Valve Control
will be carried out at the end of MRT
time. The menu option
MRT,
in the
Measurement
menu, displays the remaining time before
than MRT time ends
In the MRT time, operation in
1oo1
architecture if a further analogue channel fails (due to
over-under range) and
Valve Control
if also the surviving analogue channel fails
In the MRT time,
Valve Control
if comparison between the two channels fails
o
2oo3
architecture:
Local alarm and display of type of fault
Switch-over of Monitor relay
Exclusion of damaged channel
Operation in
1oo2
architecture for a maximum time equal to MRT. Correct system must be
restored (repair or replace the device) or
Valve Control
will be carried out at the end of MRT
time. The menu option
MRT,
in the
Measurement
menu, displays the remaining time before
than MRT time ends
-
In the MRT time,
Valve Control
will be carried out if the remaining analogue channels
fail (due to over/under range or out of comparison)