![DV Systems G20 Installation And Start-Up Data Download Page 28](http://html.mh-extra.com/html/dv-systems/g20/g20_installation-and-start-up-data_2543814028.webp)
45 3/16"
49 7/16"
46 3/8"
51 5/8"
22 1/8"
EMERGENCY
STOP
CSC300
CONTROLLER WITH
Y-DELTA START
REMOVABLE
SERVICE
DOOR
LIFTING POINTS
AIR
OUTLET
3/4"NPT
26 1/8"
28"
4X 1/2" HOLE
REMOVABLE
SIDE PANEL
2 9/16"
16 5/16" 10 5/16"
8 11/16"
7 11/16"
POWER IN
1" CONDUIT
OPENING
REMOVABLE
TOP PANEL
DUCTIBLE EXHAUST AIR
OUTLET WITH 1/4"
MOUNTING INSERTS
18 1/2"
7 7/8"
11 5/8"
15 1/4"
14 1/4"
REMOVABLE
SIDE PANEL
AIR INTAKE OPENING WITH
1/4" MOUNINTING INSERTS
REMOVABLE
REAR PANEL
INSTALLATION REQUIREMENTS
1. MAINTAIN 3 FEET DISTANCE FROM WALLS
AND OTHER OBJECTS FOR PURPOSE
OF COOLING AND SERVICING
2. COMPRESSOR MUST BE LEVEL AND
ANCHORED DOWN TO SOLID LEVEL FLOOR.
3. AMBIENT CONDITIONS:
10ºC (50ºF) MIN. 40ºC (104ºF) MAX.
4. APPROACH TEMP. FROM TANK 5ºC (41ºF).
MODEL
NO.
HP
PRESSURE
PSI
SCFM @ MAX.
PRESSURE
NOMINAL
SOUND @
1 METRE
MOTOR NAMEPLATE AMP
WEIGHT
LBS
3-PHASE
200V
230V
460V
575V
G20
20
100-120
82
67 dBA
53
46
23
18.4
1120
125-145
73
G25
25
100-120
100
68 dBA
65
56
28
22.7
1120
125-145
91
G30
30
100-120
116
69 dBA
78
68
34
27
1120
125-145
106
IMPORTANT NOTE: This print is the confidential property of DV SYTEMS, INC. It is not to be used
or reproduced in any manner, nor submitted to other parties for examination without the prior
approval of DV SYSTEMS, INC. DV SYSTEMS, INC. is continually trying to improve its products,
specifications subject to change without notice.
DESCRIPTION OF DRAWING
DRAWING NO.
SHT NO REV.
NAME OF PROJECT
DRAWN BY CHECKED BY
DATE
SCALE
G20-30 SCREW COMPRESSOR
LT
2/13/17
N.T.S
SALES-ENGINEERING DRAWING
G20 G25 G30