34
RMO60TD DV-Win Software
Test current adjustment
Selecting
“Enable current adjustment” option enables resetting of test current to selected value. In that
way it is possible to test desired tap changer position with specified test current. This is useful when the
stabilization process settles at the current value different from the selected. The procedure is as follows:
click
ADJUST
and then
OMEGA.
Afterwards click
PAUSE
and delete the last result from table. Then
return to previous tap position at the tap changer, and by pressing
OMEGA
again the new tap position is
measured with the adjusted test current.
Settings
During every tap changer test with DV-Win, the dynamic resistance graph is automatically generated.
This graph will be named
auto_save_date_and_time.tcp
and it will be saved in \\My Documents\DV-
Power\RMOT folder by default. In case the test is interrupted for any reason, this file will show the
dynamic resistance graph until the last successfully completed tap changer transition. If Continuous
recording mode is selected, the file will be named
auto_save_date_and_time_cont.tcp
In the Settings menu of DV-Win it is possible to turn off the Auto Save feature. This menu also allows to
change the folder where Auto Save files are saved.
The “Memory location” tab in the Settings menu enables the user to set a different device memory
location where the results will be saved.