20
RMO60TD Getting Started
The Tap Changer Control Unit is actually a pair of relays, one for the UP direction, and one for the
DOWN direction. The brown wire is common for both relays. Pressing the
UP
button closes the relay
between the yellow wire and the brown wire. Pressing the
DOWN
button closes the relay between the
green wire and the brown wire.
When the appropriate connection is done, the operator has just to press
UP/DOWN
on the Tap Changer
Control Unit to change the tap position.
6.5
External data exporting to USB flash drive
To export the data from internal memory of RMO60TD device to the USB flash drive, plug in the USB
flash drive into the RMO60TD device and press
button. The RMO60TD will display the USB flash
drive menu is it is shown on the screen below.
Move the cursor from the Test Record position to the Test Reading position pressing
SET
. Select the
Test Reading/Record in between the result will be exported to the USB Flash drive. The results that are
located in the range between these memory locations (Test Readings/Records), including the chosen
memory locations, will be transferred to the USB Flash drive.
The file which is saved to the USB Flash drive is automatically named by the date of the test.
Figure 6-24:
USB FLASH
DRIVE
menu
Figure 6-23: Connecting
Tap Changer Control
cable
Tap Changer
Control Unit
inside the
RMO60TD