15
RMO200D Getting Started
For Continuous Test, first time when the measured resistance is equal or greater than maximum assigned
value, RMO200D automatically stops the test and changes to the
Rmax
to display the last measured
resistance equal or greater than maximum assigned value and time of obtaining that.
The red LED lights continuously and the alarm buzzer is activated indicating that assigned maximum
value in
Rmax
menu is exceeded (or equaled).
6.7 Viewing Results of Previous Tests
RMO200D stores up to 500 test results. They can be viewed using the
Memory
menu at memory positions
000 ... 499.
Selecting a memory position on the
Memory
menu displays:
• the memory position of these results,
• the test object‟s measured resistance,
• the time of test (for continuous test),
• the current fed into the test object,
• the date and time,
of this particular test.
Figure 6-14:
The
Memory
menu
showing the previously
saved test results of
memory, position
012
for
Single or CC test and
020
for Continuous test