DUYAR HYDROPHORE Installation, Maintenance And Operation Manual Download Page 8

6

HYDROPHORE 

CONTROL PANEL

INSTALLATION, MAINTENANCE and OPERATION GUIDE

Press the 

 button in the General Settings menu, the 

text Voltage On starts to flash and the value next to it 
can be changed with the help of the 

 arrow keys, 

after the change is completed, by pressing the 

 

button value is memorized. 

 arrow keys are used 

to find the parameter we want to change and when 
the parameter is hovered, the 

 key is pressed and 

the text starts to flash, in this case the value is changed.

Voltage On:

 It is the voltage-on time setting. Waiting 

time for automatic reset when the voltage values 
measured when the system is in fault state due to 
voltage error again within the desired limits.

Voltage Off:

 It is the voltage error tripping time setting. 

When the measured voltage values go out of the set 
values, it is the waiting time to turn off. It is necessary 
in order not to take the pump off frequently in case of 
instantaneous fluctuations.

SSR On: 

It is the liquid level (SSR) reset time setting. It is 

the waiting time setting for automatic reset when the 
water comes back when the system is in a malfunction 
state due to dehydration.

SSR Off:

 It is the liquid level error tripping time setting. 

When the water in the tank or well runs out, it is the 
time to wait for the circuit to go out.

Demerage:

 Inrush current time setting. During the 

period set here, the currents drawn from the moment 
the pump starts up for the first time cannot be 
compared with the set values.

Current Delay:

 Current fault trip time setting. When 

the lower or upper current goes out of the set value, the 
time setting for stopping the motor is set in seconds.

Start Delay:

 When the signal comes from the pressure 

switch, the pumps are activated as late as the set time 
for the time set here.

Stop Delay:

 When the signal from the pressure switch 

is lost, it turns off the pumps within the set time.

Reset Time:

 Reset time setting allows us to set how 

long it waits for the system to be activated again when 
it fails due to current error. The setting is in seconds.

Reset-2:

 It is the reset number setting.

Salt:

 Ability to limit the number of pumps on and off 

in 1 hour.

Pump Change:

 It is the changeover time setting for 

pumps operating in circulation mode.

The automatic test setting is pressed, the 

 button is 

pressed, the test factory setting is passive, when we press 

the set button, the Test text starts to flash. appears as 

a clock. The run time setting allows us to set how long 

(seconds) the pump will run. Pump operation active or 

passive option is selected by pressing the 

 

arrow key 

and the 

 key is pressed, it automatically saves.

Transmitter Setting is adjusted with the help of 

arrow keys while the text "Sensor available or No sensor" 
is flashing, and it is stored by pressing the 

 key. If 

the sensor is selected, the system now works with the 

transmitter and does not read the pressure switch input.

Maximum:

 Pressure transmitter maximum (label) 

value, enter 16 bar for 16 bar transmitter.

Set Valuei:

 Pump stop set pressure value.

Hys Value:

 Pressure hysteresis adjustment. For 

example, if our set pressure is 8.0 bar hysteresis 1.0, 

then 1 pump works at 7.0 bar, 2 pumps work at 6.0 

bar, and 3 pumps at 5.0 bar.

Operation Mode Selection, operation selection is made 
with the help of 

 arrow keys according to the 

pump used. Press the  

 button and it will save 

automatically.

Hydrophore:

 Standart hidrofor motorlarında bu mod 

seçilmelidir.

Hydr Ptc: 

If there is PTC protection in booster 

pumps, this mode should be selected. Otherwise, PTC 

protection will not do..

P + Joker: 

It is the choice of 1 main and 1 wildcard in fire systems.

Waste Water:

 This mode should be selected for 

wastewater pumps. When this mode is selected, water 

leakage and Ptc inputs are active.

Waste Water Stop Fit:

 In the selection of waste water 

with stop floater, water leakage and Ptc inputs become 

active and the system stops according to the stop floater.

Floater / SSR selection is the float or SSR electrode 

protection selection setting of the device. Selection

is made with the help of the arrow key and saved by 

pressing the set key.

General Settings

Voltage On = 05

Auto Test Settings

Test = Active

Floater / SSR Secim

Floater

Transmitter Set

There is Sensor

Operation Mode Select

Hydrophore

6. SETTINGS MENU

Press the 

 button to enter the menu.

Summary of Contents for HYDROPHORE

Page 1: ...INSTALLATION MAINTENANCE and OPERATION GUIDE HYDROPHORE CONTROL PANEL...

Page 2: ...ORE CONTROL PANEL INSTALLATION MAINTENANCE and OPERATION GUIDE www duyarpompa com Control panels to get the best results this manual information must read carefully This manual all your problems can h...

Page 3: ...TRANSPORT STORAGE MONTAGE 3 1 1 Transfer 3 1 1 Transport 3 1 3 Storage 3 1 4 Montage 3 2 OPERATING 3 3 MAINTENANCE 3 3 1 Monthly Maintenance 3 4 GENERAL INFORMATION OF THE PRODUCT 4 4 1 General Speci...

Page 4: ...ble damaged and torn Do not place heavy objects on the power cord and do not make an operation on the cable or injure Cables may be damaged and may cause a fire or electric shock In such cases please...

Page 5: ...ld be checked for any damage during transport If the clipboard contains a damaged or missing damage assessment report should be given written information to the shipping company our company 1 3 Storag...

Page 6: ...ime at automatic resetting Ability to reset automatically in error cases and to set the reset number Automatic manuel selection Manuel operation when pressing the test button at manuel Protection agai...

Page 7: ...n settings menu with the help of the button the past fault information is highlighted and by pressing the down arrow button the most recent fault of the device always moves to the first place A total...

Page 8: ...Reset 2 It is the reset number setting Salt Ability to limit the number of pumps on and off in 1 hour Pump Change It is the changeover time setting for pumps operating in circulation mode The automati...

Page 9: ...ction Insulation Assembly Protection Class Working Altitude PART NAME 230 V 380 VAC 50 60Hz 6VA 20 C to 55 C 10 500 V AC 1 1 30 sec 2 X 16 LCD Screen and Leds Terminal Connection 5 A 250 VAC Resistive...

Page 10: ...E SWITCH FLOATER 6 7 8 3 4 5 2 1 CONTROL PANEL SELENOID U V W X Y Z 17 18 16 15 N COM U V W X Y Z 14 11 12 13 10 9 ERR L1 L2 L3 MAIN 380V AC 50 60Hz PRESSURE SWITCH FLOATER 6 7 8 3 4 5 2 1 CONTROL PAN...

Page 11: ...vibration storage physical collisions damage and malfunction caused by chemical factors and environmental conditions 6 Fire lightning floods earthquakes and other natural disasters damage and malfunc...

Page 12: ...2021 11 1 WE ARE SENSITIVE TO LIFE...

Reviews: