HYDROPHORE
CONTROL PANEL
INSTALLATION, MAINTENANCE and OPERATION GUIDE
5
6. SETTINGS MENU
The Voltage Settings menu appears. When we press
the
button once, the above screen appears.
The upper voltage text starts to flash. In this case, the
value can be changed with the help of the
arrow
keys. Press the
button and save the High Voltage
set, and the following screen appears automatically.
When we press the Lower Voltage Setting
button,
the Lower Voltage setting starts to flash, in this case
the
arrow keys, The value can be changed with
the help of Press the
key, save the lower voltage set
and return to the menu page.
In order to change the current settings, press the
button and the current settings appear. Press the
button. P.1 saves the upper current setting by setting,
and the following screen appears automatically.
When the Sub-Stream setting
button is pressed,
the P.1 subtitle starts to flash. In this case, the value
can be changed with the help of the
arrow
keys. Press the
key, save the P.1 Sub stream set and
return to the menu page.
From the historical fault information settings menu,
with the help of the
button, the past fault
information is highlighted, and by pressing the
down arrow button, the most recent fault of the device
always moves to the first place. A total of 20 records are
stored in memory.
Language selection is pressed,
button is pressed,
Language Selection is highlighted with the help of the
arrow button in the settings menu, and the menu
is entered by pressing the
button. The desired
language is selected with the help of the
arrow
keys and automatically saved by pressing the
key.
Press the Working Hours
button, and in the settings
menu, use the
arrow key to scroll to the Working
Times. By pressing the
button, the menu is entered.
The operating time of the pumps is displayed in hours.
A password is required by the system to enter the
general settings. When the
button is pressed,
a 4-digit password is requested. If the password is
incorrect, the system automatically discards it from the
menu. When the password is entered, the screen on
the next page appears.
Voltage Settings
High Volt=250V
History Fault
01= High Current
Language Select
English
Operating Time
P1=0h / 0S
P2=0h / 0S
Voltage Settings
Low Volt=180V
Current Settings
P.1 High =15.0A
Current Settings
P.1 Low =01.0A
Press the
button to enter the menu.
Enter Password