33
Choosing the right power cord
Long or thin cords can drain the power provided to an electrical device by the generator. When
using such cords, allow for a slightly higher rated wattage requirement for the electrical device. See
table below for recommended cords based on the power requirement of the electrical device.
DEVICE REQUIREMENTS
WIRE GAUGE BY LENGTH (ft.)
AMPS
WATTS (120/240V)
10
25
50
100
150
5
600/1200
18
16
14
12
10
10
1200/2400
16
14
12
10
8
15
1800/3600
14
12
10
8
6
20
2400/4800
12
10
8
6
4
25
3000/6000
10
8
6
4
4
30
3600/7200
8
6
4
4
NR
40
4800/9600
6
4
4
NR
NR
50
6000/1200
4
4
2
NR
NR
*NR = NOT RECOMMENDED
Summary of Contents for DS4000S
Page 2: ......
Page 5: ......
Page 19: ...19 Test handle pivot The handle should easily flip up and down after installation 1 ...
Page 28: ...28 ...
Page 34: ...34 ...
Page 37: ...MAINTENANCE LOG Date Generator Hours Maintenance Performed 37 ...
Page 56: ...WIRING DIAGRAM 56 ...
Page 57: ...57 ...
Page 63: ......
Page 64: ...5800 Ontario Mills Parkway Ontario CA 91764 United States 844 DUROMAX ...