background image

DuroZone

 

SMZ-AC WIRING INSTRUCTIONS PAGE 1

SMZ-AC INSTALLATION INSTRUCTIONS

Congratulations on purchasing a Duro Zone SMZ-AC Control System. The SMZ-AC Panel together with Duro Zone Multiline 

Dampers will provide year round comfort for your customer. Following are simple step-by-step installation instructions and 

wiring diagrams for the SMZ-AC System.

For your convenience, your SMZ-AC System is shipped “knocked down”. Do not mount the circuit board to the box before 

attaching the box to the wall or the mounting holes will be inaccessible.

 

1. 

Mount the panel box to any flat surface.

 

2.

 Mount the circuit board to the panel box with the nylon standoffs provided.

 

3. 

Strip the wires and attach them to their respective terminals. 

 

4. 

Snap the cover onto the panel box.

WIRING

Your SMZ-AC Panel has 4 distinct terminal strips for wiring. One is for the equipment and one is for each zone thermostat 

and damper. Simply follow the instructions below using the wiring diagram included for reference.

EQUIPMENT

The upper left terminal strip is for wiring the equipment to the SMZ-AC Panel.

FROM TOP TO BOTTOM:

Terminal “C” goes to the “C” or common side of the equipment transformer.

Terminal “R” goes to the “R” or hot side of the equipment transformer

Terminal “W” goes to the furnace relay (W).

Terminal “Y” goes to the compressor relay (Y).

Terminal “G” goes to the fan relay (G).

Terminal “W2” goes to 2nd stage heat relay (see special wiring for Heat Pumps)

Terminal “O” goes to changeover valve relay (see special wiring for Heat Pumps)

Terminals 1 and 2 go to a separate 24-volt transformer used to power the Duro Zone Dampers.

Duro Zone’s PT-40, 24-volt 40VA transformer, (Part #35054), is recommended.

ZONE 1

The lower left terminal strip is for Zone 1. The Zone 1

Thermostat must have a heat/cool  fan on/auto switchable

sub-base. Duro Zone’s DRSMS Sub-Base, Part #35181, with a 

Duro Zone DRS Thermostat, Part #35187, is recommended.

FROM TOP TO BOTTOM:

 

SMZ-AC Terminal “W” goes to “W” on Zone 1 Thermostat.

SMZ-AC Terminal “R” goes to “R” on Zone 1 Thermostat.

SMZ-AC Terminal “Y” goes to “Y” on Zone 1 Thermostat.

SMZ-AC Terminal “G” goes to “G” on Zone 1 Thermostat.

SMZ-AC Terminal “W2” goes to “W2” on Zone 1 Thermostat.

SMZ-AC Terminal 1 goes to Terminal 1 of Zone 1 Damper Motor.

SMZ-AC Terminal 2 goes to Terminal 2 of Zone 1 Damper Motor.

SMZ-AC Terminal 4 goes to Terminal 4 of Zone 1 Damper Motor.

ZONE 2&3

The upper right terminal strip is for Zone 2. The lower right 

terminal strip is for Zone 3. The Zone 2 & 3 Thermostat 

must have a heat/cool switchable sub-bases. Duro Zone’s 

DRSHCS Sub-Base, Part #35182, with a Duro Zone DRS 

Thermostat, Part #35187, is recommended.

 

FROM TOP TO BOTTOM:

SMZ-AC Terminal  W goes to Terminal “W” of Thermostat.

SMZ-AC Terminal  R goes to Terminal “R”  of Thermostat.

SMZ-AC Terminal  Y goes to Terminal “Y” of Thermostat.

SMZ-AC Terminal “W2” goes to “W2” of Thermostat.  

SMZ-AC Terminal 1 goes to Terminal 1 of Zone Damper Motor.

SMZ-AC Terminal 2 goes to Terminal 2 of Zone Damper Motor.

SMZ-AC Terminal 4 goes to Terminal 4 of Zone Damper Motor.

Summary of Contents for DuroZone SMZ-AC

Page 1: ... MODEL SMZ AC ZONE CONTROL SYSTEM Corporation DuroZone is a division of DuroZone DuroZone PART 35229 ...

Page 2: ...pecial wiring for Heat Pumps Terminal O goes to changeover valve relay see special wiring for Heat Pumps Terminals 1 and 2 go to a separate 24 volt transformer used to power the Duro Zone Dampers Duro Zone s PT 40 24 volt 40VA transformer Part 35054 is recommended ZONE 1 The lower left terminal strip is for Zone 1 The Zone 1 Thermostat must have a heat cool fan on auto switchable sub base Duro Zon...

Page 3: ...DuroZone SMZ AC WIRING INSTRUCTIONS PAGE 2 ...

Page 4: ...DuroZone SMZ AC WIRING INSTRUCTIONS PAGE 3 ...

Page 5: ... switch per zone These switches will allow a zone damper to remain in either the open or closed position when the system board is at rest The SMZ AC allows the installer or home owner to choose the position of his system s damp ers This feature can inhibit migration of air into spaces not desired for seasonal purposes or when a zone is not in use The SMZ AC Zone System has a built in safety featur...

Page 6: ...Z AC Panel Zone 1 Terminal Strip Zone 1 will be calling for cooling All zone dampers except zone 1 will close and the air conditioning will come on The Heat Lockout Relay Equipment 1 Relay and Zone 1 Relay will activate Red indicator light will glow Zones 2 or 3 can be activated by jumping R Y at the SMZ AC Zone 2 or Zone 3 Terminal Strips If the air conditioning does not activate test for 24 volt...

Page 7: ... AC La Zona 1 demandará calor Todos los dampers excepto el de la Zona 1 se cerrarán y el aire acondicionado se encenderá El relé de bloqueo de calor el relé del equipo 1 y el relé de la Zona 1 se activarán Se encenderá el indicador de la luz roja Las Zonas 2 o 3 pueden activarse realizando la desviación de R e Y en las correspondientes placas de bornes de las Zonas 2 o 3 del SMZ AC Si el aire acon...

Page 8: ...para cada zona Estos conmutadores permitirán que el regulador de una zona permanezca en la posición abierto o cerrado cuando la placa del sistema está en reposo El sistema SMZ AC permite al instalador o propietario elegir la posición de los dampers del sistema Esta función permite inhibir la migración de aire a espacios no deseados adecuándose a las condiciones climáticas o cuando una zona no se e...

Page 9: ...24 VAC 40 Pieza No 35054 120 VAC 120 VAC Bomba de calor Retardo de tiempo Retardo de tiempo Relé Pieza No 35055 Retardo de tiempo Pieza No 35215 Ventilador impelente NOTA La mayoría de los termostatos con R W Y y G funcionarán con este sistema en cualquier zona Los termostatos deben contar con una sub base de conmutación y o banda inactiva entre los ajustes de calor y frío ZONA 1 ZONA 3 ZONA 2 BLO...

Page 10: ...7 con DRSHCS 35182 DRS 35187 con DRSMS 35181 3WT 35052 con MSSB 35214 TERMOSTATO DE REDUCCIÓN 35173 Calor Ventilador 120 VAC ZONA 3 ZONA 2 ZONA 1 NOTA La mayoría de los termostatos con R W Y y G funcionarán con este sistema en cualquier zona Los termostatos deben contar con una sub base de conmutación y o banda inactiva entre los ajustes de calor y frío 24 VAC Calor Compresor ZONA 1 ZONA 3 ZONA 2 ...

Page 11: ...s para alimentar los dampers DuroZone Se recomienda el uso de un transformador PT 40 de 24 voltios 40VA Pieza No 35054 de DuroZone ZONA 1 La placa de bornes inferior izquierda es para la Zona 1 El termostato de la Zona 1 debe contar con una sub base conmutable calor frío con ventilador encendido o en modo automático Se recomienda la sub base DRSMS Pieza No 35181 de Duro Zone con un termostato DRS ...

Page 12: ... MODELO SMZ AC SISTEMA DE CONTROL DE ZONAS Corporation DuroZone es una división de DuroZone DuroZone PIEZA N o 35229 ...

Reviews: