Duro Dyne DuroZone SMZ-AC Quick Start Manual Download Page 5

DuroZone

 

SMZ-AC WIRING INSTRUCTIONS PAGE 4

SMZ-AC  OPERATION

The SMZ-AC is a simple autochangeover zoning system incorporating individual thermostats and zone dampers to provide 

comfort and economy.

The SMZ-AC is a first call - first served system, ie. If a zone calls for cooling, heating calls are locked out and the system will 

satisfy all cooling calls. When satisfied the system will then switch to heat and satisfy those calls.  When  all zones are satisfied, 

heating and cooling, each zone damper will be in the position set by the Damper Switch, (see below). If any zone calls, that 

damper will open, or remain open, and all others will close. Should another zone call, for the same equipment as the first zone 

to call, its corresponding damper will open. Upon satisfaction of the zone (s) all dampers will return to the position set with 

the Damper Switch, (see below).

With a call in the heat mode, “R” makes to “W” in the equipment section, activating the furnace relay. The fan will be con-

trolled by the fan limit switch in the furnace.

With a call in the cool mode, “R” makes to “Y” activating the Compressor and “R” makes to “G”, activating the fan and “R” 

makes to “O” activating the changeover valve if using a heat pump.

When the fan switch on the Zone One Sub-Base is in the “on” position, “R” makes to “G” and the fan provides constant air 

circulation.

NOTE: If all damper switches are set in “closed”, “(C)” position, the fan will not operate in the “Fan On” 

position.

DAMPER SWITCHES

The SMZ-AC Zone System is equipped with individual zone damper control switches. These switches are located to the left of 

the zone relays; one switch per zone. These switches will allow a zone damper to remain in either the open or closed position 

when the system board is at rest. The SMZ-AC allows the installer or home owner to choose the position of his system’s damp-

ers. This feature can inhibit migration of air into spaces not desired, for seasonal purposes, or when a zone is not in use.

The SMZ-AC Zone System has a built-in safety feature. At least one zone damper switch must be in the open position for the 

“fan on” switch on the master thermostat to be operational. If all switches are set to “closed” (c), the constant fan circuit is 

disabled. This safety feature removes the possibility that the air handler could be damaged due to cavitation, or by a restricted 

air distribution system.

SMZ GAS/ELECTRIC JUMPER

Your SMZ panel includes a jumper block labeled JP1. The purpose of this jumper is to configure the operation of the fan for 

normal gas /oil heating equipment or for electric heating equipment.

When Placed in the “G” position (default) the fan is controlled by the equipment in the heat mode (conventional operation).

When Placed in the “E” position the fan will come on immediately with the call for heating (electric heat operation).

ORDERING INFORMATION

Duro Zone’s SMZ Panels can be ordered for a variety of applications.

35235: 

JTZ-HPSW -1  JTZ-HP Panel configured for three zone heat pumps.

35226: 

SMZ-2 SW -1  SMZ-SW Panel configured for two zones.

35227: 

SMZ-3 SW -1  SMZ-SW Panel configured for three zones.

35228: 

SMZ-4 SW -1  SMZ-SW Panel configured for four zones.

35229: 

SMZ-AC -1 

SMZ-SW Panel configured for three zone autochangeover.

Damper is closed

when zone is satisfied.

 

Damper is open

when zone is satisfied.

O

C

O

C

JP1

 

E

Gas Mode - Normal operations. (Default Settings)

Electric Mode - Fan comes on immediately with heat call.

 

E

Summary of Contents for DuroZone SMZ-AC

Page 1: ... MODEL SMZ AC ZONE CONTROL SYSTEM Corporation DuroZone is a division of DuroZone DuroZone PART 35229 ...

Page 2: ...pecial wiring for Heat Pumps Terminal O goes to changeover valve relay see special wiring for Heat Pumps Terminals 1 and 2 go to a separate 24 volt transformer used to power the Duro Zone Dampers Duro Zone s PT 40 24 volt 40VA transformer Part 35054 is recommended ZONE 1 The lower left terminal strip is for Zone 1 The Zone 1 Thermostat must have a heat cool fan on auto switchable sub base Duro Zon...

Page 3: ...DuroZone SMZ AC WIRING INSTRUCTIONS PAGE 2 ...

Page 4: ...DuroZone SMZ AC WIRING INSTRUCTIONS PAGE 3 ...

Page 5: ... switch per zone These switches will allow a zone damper to remain in either the open or closed position when the system board is at rest The SMZ AC allows the installer or home owner to choose the position of his system s damp ers This feature can inhibit migration of air into spaces not desired for seasonal purposes or when a zone is not in use The SMZ AC Zone System has a built in safety featur...

Page 6: ...Z AC Panel Zone 1 Terminal Strip Zone 1 will be calling for cooling All zone dampers except zone 1 will close and the air conditioning will come on The Heat Lockout Relay Equipment 1 Relay and Zone 1 Relay will activate Red indicator light will glow Zones 2 or 3 can be activated by jumping R Y at the SMZ AC Zone 2 or Zone 3 Terminal Strips If the air conditioning does not activate test for 24 volt...

Page 7: ... AC La Zona 1 demandará calor Todos los dampers excepto el de la Zona 1 se cerrarán y el aire acondicionado se encenderá El relé de bloqueo de calor el relé del equipo 1 y el relé de la Zona 1 se activarán Se encenderá el indicador de la luz roja Las Zonas 2 o 3 pueden activarse realizando la desviación de R e Y en las correspondientes placas de bornes de las Zonas 2 o 3 del SMZ AC Si el aire acon...

Page 8: ...para cada zona Estos conmutadores permitirán que el regulador de una zona permanezca en la posición abierto o cerrado cuando la placa del sistema está en reposo El sistema SMZ AC permite al instalador o propietario elegir la posición de los dampers del sistema Esta función permite inhibir la migración de aire a espacios no deseados adecuándose a las condiciones climáticas o cuando una zona no se e...

Page 9: ...24 VAC 40 Pieza No 35054 120 VAC 120 VAC Bomba de calor Retardo de tiempo Retardo de tiempo Relé Pieza No 35055 Retardo de tiempo Pieza No 35215 Ventilador impelente NOTA La mayoría de los termostatos con R W Y y G funcionarán con este sistema en cualquier zona Los termostatos deben contar con una sub base de conmutación y o banda inactiva entre los ajustes de calor y frío ZONA 1 ZONA 3 ZONA 2 BLO...

Page 10: ...7 con DRSHCS 35182 DRS 35187 con DRSMS 35181 3WT 35052 con MSSB 35214 TERMOSTATO DE REDUCCIÓN 35173 Calor Ventilador 120 VAC ZONA 3 ZONA 2 ZONA 1 NOTA La mayoría de los termostatos con R W Y y G funcionarán con este sistema en cualquier zona Los termostatos deben contar con una sub base de conmutación y o banda inactiva entre los ajustes de calor y frío 24 VAC Calor Compresor ZONA 1 ZONA 3 ZONA 2 ...

Page 11: ...s para alimentar los dampers DuroZone Se recomienda el uso de un transformador PT 40 de 24 voltios 40VA Pieza No 35054 de DuroZone ZONA 1 La placa de bornes inferior izquierda es para la Zona 1 El termostato de la Zona 1 debe contar con una sub base conmutable calor frío con ventilador encendido o en modo automático Se recomienda la sub base DRSMS Pieza No 35181 de Duro Zone con un termostato DRS ...

Page 12: ... MODELO SMZ AC SISTEMA DE CONTROL DE ZONAS Corporation DuroZone es una división de DuroZone DuroZone PIEZA N o 35229 ...

Reviews: