CLEARANCES

Always allow at least a 2-inch air-space 

clearance between DuraChimney II pipe 

and any combustible materials. Never fill any 

required clearance space with insulation or 

any other materials. Combustible materials 

include, but is not limited to, lumber, plywood, 

sheetrock, plaster and lath, furniture, curtains, 

electrical wiring, and building insulation.  

PERMITS

 

Contact your local Building Official or Fire 

Official regarding permits, restrictions, and 

installation inspections in your area.  

CHIMNEY  APPLICATIONS 

DuraChimney II is a complete chimney 

system tested and listed to test procedures 

UL 103 and ULC S604.  In the United States, 

DuraChimney II can be used with masonry 

fireplaces or appliances fueled by oil, gas, 

coal, or wood that have been tested and listed 

for use with a UL 103 chimney system.  In 

Canada, DuraChimney II can be used with 

listed oil & gas fired appliances or wood-

burning fireplaces requiring a Type A Chimney, 

in accordance with ULC S604.

DuraChimney II may also be listed with 

some factory-built fireplaces. Check with the 

fireplace manufacturer if DuraChimney II 

can be used on their fireplaces, and if there 

are any limitations of use. Do not use with 

forced draft or positive-pressure appliances.  

The DuraChimney II system is designed to 

extend vertically with a maximum of one (1) 

offset (two elbows total) of up to 30° from 

vertical.  DuraChimney II is listed under UL re-

examination Service number mh7399.

EQUIPMENT  &  MATERIALS

Drill / Driver

hammer   

 

 

Caulking Gun

plumb Bob 

Screwdrivers (phillips & Standard)

Tin Snips 

Saber or Keyhole Saw

Level  

Dependable Ladder

Tape measure 

proper Gloves and Shoes

eye protection

materials you may need: 

non-hardening Waterproof Sealant  

8-penny nails, 

600

°

F rTV Silicone Sealant 

Roofing Nails

#8, 2-1/2” & 1-1/2” Wood Screws 

 

 

INSTALLATION  NOTES 

proper planning for your DuraChimney 

II installation will result in greater safety, 

efficiency, and convenience, as well as 

saving time and money.  you must use only 

authorized DuraChimney II parts to maintain 

a listed chimney system.  Do not mix parts 

or try to match with other products or use 

improvised solutions.  Do not install damaged 

or modified parts.  Practice good workmanship.  

Sloppy work could jeopardize your chimney’s 

safety.  Keep electrical wiring and building 

insulation away from all chimneys. When 

deciding the location of your chimney, try to 

avoid modifications to roof beams and other 

structural components of the building. Contact 

either your dealer or Simpson Dura-Vent 

directly if you have any questions. 

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for DuraChimney II

Page 1: ...himney ii Complete Venting Solutions for the Hearth Industry Installation Instructions Air Cooled All Fuel Chimney for Fireplaces NorthlineExpress com http www northlineexpress com Toll Free 1 866 667...

Page 2: ...Chimney II is listed to UL 103 and ULC S604 standards for use on masonry fireplaces which burn wood oil coal or gas Some factory built fireplaces may be listed with DuraChimney II Check to the firepla...

Page 3: ...ce Installation Frame Opening Chart 6 Chimney Sizing Chart 11 Elbow Offset Installation 13 Elbow Offset Chart 14 Chimney Maintenance 15 Warranty 16 Air cooled all fuel chimney for fireplaces DuraChimn...

Page 4: ...or positive pressure appliances The DuraChimney II system is designed to extend vertically with a maximum of one 1 offset two elbows total of up to 30 from vertical DuraChimney II is listed under UL R...

Page 5: ...rough floors of buildings requiring the protection of vertical openings shall be enclosed with approved walls having a fire resistance rating of not less than one hour when such chimneys are located i...

Page 6: ...on which to attach the Anchor Plate or Anchor Plate If the top of the masonry does not have a level surface then you will need to modify the masonry accordingly Center the Anchor Plate over the mason...

Page 7: ...ve cut Frame openings at each floor level above the Fireplace Fig 4 These openings are to hold the Firestop and Attic Insulation Shield Locate each opening by dropping a plumb bob to the four corners...

Page 8: ...ections Fig 6 Do not penetrate the inner liner of the chimney Use a Wall Strap every eight 8 feet of chimney height 9 Supplementary Support and Stabilizer Install a Supplementary Support if total chim...

Page 9: ...cannot fit or is not used you must enclose the attic portion of the chimney in a framed enclosure always maintain 2 air space clearance to combustibles If the chimney is fully enclosed through the at...

Page 10: ...g members are further away from the chimney than 2 center the Roof Radiation Shield to the chimney on the framing member and secure in place with screws or nails 12 Attach Flashing For chase enclosure...

Page 11: ...le is 12 diameter pipe T W H T W H 8 7 6 30 16 14 20 8 10 15 12 10 50 40 30 24 48 60 36 42 72 HEIGHT 36 30 42 24 48 18 W IDTH 18 20 22 24 20 18 60 72 84 84 HEIGHT FEET CHIMNEY FIREPLACE OPENING INCHES...

Page 12: ...he Flashing Fig 15 Slide the Storm Collar down over the chimney to the top of the Flashing The Storm Collar must be installed 1 off the Chase Top Flashing to provide proper ventilation Fig 15 Tighten...

Page 13: ...1 Attach Elbows Attach Elbow to Chimney Section or other Elbow by mating the male and female ends with each other and using the 4 sheet metal screws provided Attach one Elbow to the Chimney Section b...

Page 14: ...hes Rise Inches Offset Inches Rise Inches 15 0 2 20 2 21 2 21 2 21 15 12 5 31 5 31 5 32 5 32 15 18 7 37 7 37 7 38 7 36 15 36 11 54 11 55 11 55 11 55 15 48 14 66 14 66 14 67 14 67 30 0 5 22 6 22 6 24 6...

Page 15: ...attach the top lid of the Cap to the cap s legs 5 Coal To reduce corrosion in chimneys where coal is burned clean the chimney thoroughly within 48 hours of shutting down the appliance for the season 6...

Page 16: ...ro PelletVent CornVent DuraLiner DuraFlex DirectVent Pro Type B Gas Vent DuraConnect or DVL with dated proof of purchase Purchaser s sole remedy is replacement of component fittings and chimney pipe l...

Reviews: