background image

12

Top Collar Section to the field-fabricated chase 

top with sheet metal screws or rivets (Fig. 14)

Seal Chase Top Collar Section to chase top with 

non-hardening waterproof sealant to ensure a 

weather tight connection. Additional screening 

as needed for field-fabricated chase covers is 

allowed. Additional ½” minimum spacers can be 

field-fabricated as needed out of 24 GA sheet 

metal or other suitable non-combustible material. 

Additional non-combustible structural supports 

can be field-fabricated to help support the chase 

top flashing if needed, provided the air ventilation 

requirements are maintained. Secure the Chase 

Top Flashing to the chase with at least (3) screws 

or nails per side. When installed, the bottom of 

the Chimney Cap must be at least 6” above the 

Chase Top Flashing (Fig. 15).

13.  Finish Top:  Apply a non-hardening 

waterproof sealant around the chimney at the 

point where the Storm Collar will meet the 

chimney just above the Flashing (Fig. 15).  Slide 

the Storm Collar down over the chimney to the 

top of the Flashing.  The Storm Collar must be 

installed 1” off the Chase Top Flashing to provide 

proper ventilation (Fig. 15). Tighten the bolts 

of the Storm Collar and seal the Storm Collar 

against the Chimney with sealant.  Be sure 

Chimney and Offsets are properly supported. 

Attach the Chimney Cap onto the top of the 

chimney by setting the female end of the Cap 

onto the male end of the last Chimney Section.  

Secure the Cap by using (4) sheet metal screws 

provided (Fig. 16).  Do not push down from the 

top portion of the cap as this may damage the 

cap.  push from the lower section of the Cap if 

needed.  The Chimney Cap can be removed for 

chimney cleaning as described in the Chimney 

maintenance section of the instructions.  

14. Enclosures:  enclose chimneys where 

they pass through occupied spaces, including 

closets.  Always maintain at least a 2-inch 

Figure 16

TERMINATION

CAP

Figure 14

Figure 15

6" MIN.

COLLAR

SEALANT

STORM

OPENING

ABOVE ROOF

3' MINIMUM

CHASE TOP

  COLLAR

SEALANT

SCREW OR

POP-RIVET

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for DuraChimney II

Page 1: ...himney ii Complete Venting Solutions for the Hearth Industry Installation Instructions Air Cooled All Fuel Chimney for Fireplaces NorthlineExpress com http www northlineexpress com Toll Free 1 866 667...

Page 2: ...Chimney II is listed to UL 103 and ULC S604 standards for use on masonry fireplaces which burn wood oil coal or gas Some factory built fireplaces may be listed with DuraChimney II Check to the firepla...

Page 3: ...ce Installation Frame Opening Chart 6 Chimney Sizing Chart 11 Elbow Offset Installation 13 Elbow Offset Chart 14 Chimney Maintenance 15 Warranty 16 Air cooled all fuel chimney for fireplaces DuraChimn...

Page 4: ...or positive pressure appliances The DuraChimney II system is designed to extend vertically with a maximum of one 1 offset two elbows total of up to 30 from vertical DuraChimney II is listed under UL R...

Page 5: ...rough floors of buildings requiring the protection of vertical openings shall be enclosed with approved walls having a fire resistance rating of not less than one hour when such chimneys are located i...

Page 6: ...on which to attach the Anchor Plate or Anchor Plate If the top of the masonry does not have a level surface then you will need to modify the masonry accordingly Center the Anchor Plate over the mason...

Page 7: ...ve cut Frame openings at each floor level above the Fireplace Fig 4 These openings are to hold the Firestop and Attic Insulation Shield Locate each opening by dropping a plumb bob to the four corners...

Page 8: ...ections Fig 6 Do not penetrate the inner liner of the chimney Use a Wall Strap every eight 8 feet of chimney height 9 Supplementary Support and Stabilizer Install a Supplementary Support if total chim...

Page 9: ...cannot fit or is not used you must enclose the attic portion of the chimney in a framed enclosure always maintain 2 air space clearance to combustibles If the chimney is fully enclosed through the at...

Page 10: ...g members are further away from the chimney than 2 center the Roof Radiation Shield to the chimney on the framing member and secure in place with screws or nails 12 Attach Flashing For chase enclosure...

Page 11: ...le is 12 diameter pipe T W H T W H 8 7 6 30 16 14 20 8 10 15 12 10 50 40 30 24 48 60 36 42 72 HEIGHT 36 30 42 24 48 18 W IDTH 18 20 22 24 20 18 60 72 84 84 HEIGHT FEET CHIMNEY FIREPLACE OPENING INCHES...

Page 12: ...he Flashing Fig 15 Slide the Storm Collar down over the chimney to the top of the Flashing The Storm Collar must be installed 1 off the Chase Top Flashing to provide proper ventilation Fig 15 Tighten...

Page 13: ...1 Attach Elbows Attach Elbow to Chimney Section or other Elbow by mating the male and female ends with each other and using the 4 sheet metal screws provided Attach one Elbow to the Chimney Section b...

Page 14: ...hes Rise Inches Offset Inches Rise Inches 15 0 2 20 2 21 2 21 2 21 15 12 5 31 5 31 5 32 5 32 15 18 7 37 7 37 7 38 7 36 15 36 11 54 11 55 11 55 11 55 15 48 14 66 14 66 14 67 14 67 30 0 5 22 6 22 6 24 6...

Page 15: ...attach the top lid of the Cap to the cap s legs 5 Coal To reduce corrosion in chimneys where coal is burned clean the chimney thoroughly within 48 hours of shutting down the appliance for the season 6...

Page 16: ...ro PelletVent CornVent DuraLiner DuraFlex DirectVent Pro Type B Gas Vent DuraConnect or DVL with dated proof of purchase Purchaser s sole remedy is replacement of component fittings and chimney pipe l...

Reviews: