background image

12. Emergency Actions - Other considerations

In addition, the following items may modify the actions recommended above and, where appropriate, 

should be taken into consideration at the time of installing the apparatus:

a) It should be recognised that increasing ventilation rates may actually lead to higher levels of indoor 

carbon monoxide concentration under certain circumstances. Examples of such an occasion would be 

from a nearby vehicle exhaust or during extremely bad traffic pollution, especially in cold weather. It is 

therefore possible that outdoor conditions could be a factor in triggering domestic carbon monoxide 

alarms.

b) There may be another source of carbon monoxide emission inducing the alarm, for example

 

– a large amount of tobacco smoke,

 

– town gas,

 

– emission from a smouldering fire.

c) The alarm may be induced by other substances. (See 9. Avoiding False Alarms)

d) Particular situations could result in exposure to emissions from neighbouring premises, especially in 

multi-occupancy and multi-storey properties. There may be special problems with shared or poorly-sited 

flues, for example, which could lead to ingress of carbon monoxide from elsewhere in the same building. 

Such possibilities should be fully investigated when installing the apparatus.

e) The CHCO provides an output signal which may be used to activate an ancillary device, such as a ven-

tilation fan or gas shut-off valve. Once triggered, these devices may need to be manually reset, but this 

should not be done until the source of carbon monoxide or fuel gas escape has been identified and the 

fault corrected. 

13. Maintenance

This device should be tested periodically ideally every 6 months but a minimum of every 12 months. The 

procedure is described in 7. Operation. In the unlikely event that the CHCO fails its routine test, please 

contact Duomo technical department on 01905 797989. Advice will be given as to the best course of 

action. You will need to provide the date of purchase and the serial number of the CHCO.  

14. Anticipated Lifetime of the CHCO.

From date of supply the CHCO has an anticipated lifespan of 6 years. This will be indicated on the label 

placed on the fascia of the device during installation.  Dated stickers are provided loose in the packing. 

These must be applied by the installer of the device. 

The CHCO has an automatic end-of-life feature that raises a fault-warning signal when it is necessary to

replace the apparatus. This actuates when the return signal from either the Natural Gas Sensor or the 

carbon monoxide sensor falls outside pre-set values. If the fault light (7. Layout of Components) becomes 

lit the unit will fail safe and the CHCO must be replaced. 

15. Warranty Period

From date of manufacture the warranty period is 2 years. This is extendible to 3 years by registering this 

product online at https://duomo.co.uk/product-warranty/ .

Summary of Contents for CHCO

Page 1: ...ct Duomo CHCO Natural Gas and Carbon Monoxide detector TYPE A 96125 THIS IS AN IMPORTANT DOCUMENT IT CONTAINS INFORMATION REGARDING INSTALLATION SAFE AND PROPER OPERATION AND REGULAR CHECKING OF THIS NATURAL GAS AND CARBON MONOXIDE DETECTOR ...

Page 2: ...or tech nology The Duomo CHCO detector is ideally suited for people with some physical disability that might de lay a manual response to an alarm It is a fixed wall mounted system with a permanently connected 230 Volt electrical supply The CHCO is fitted with an output function for trig gering different ancillary devices for example Gas Shut off valve If the apparatus is installed in homes equippe...

Page 3: ...noxide sensor element 6 On Light This light flashes as soon as power is applied After 100 seconds the light stops flashing and is permanently lit until power is disconnected Note During the diagnostic warm up phase the CHCO will not detect gas 7 Fault Light Becomes lit when either the Natural Gas or the CO sensor element becomes inoperative 8 Alarm CO Light 9 Alarm Gas light 10 Cable connection Te...

Page 4: ...s such as cleaning in the area For further information see BS EN50292 and BS EN50244 Fuel Burning Appliance A A B B D D C Flue or Extractor Canopy Key to Positioning Diagram Fuel Burning Appliance This could be a Fire Cooker Boiler or any other gas fired appliance Flue or Extractor canopy Used to remove the products of combustion from the room under normal cir cumstances Dimension A 1m Dimension B...

Page 5: ...competent person This test is used to establish the correct operation of connected devices and does not replace the requirement to Test using Calibrated test gas at least once a year Testing with calibrated test gas Expose the Natural Gas sensor 3 to the a 20 LEL Test Gas This Gas can be purchased from Duomo Expose the Carbon Monoxide sensor to Carbon Monoxide test gas from 30 to 300ppm Please not...

Page 6: ...uced by a given exposure CO is rapidly ab sorbed through the lungs diffuses across the alveolar capillary membrane and is reversibly bound with haemoglobin as carboxyhaemoglobin COHb The affinity of haemoglobin for CO is over 200 times its affinity for oxygen This reduces the oxygen carry ing capacity of the blood and has an effect on the dissociation of oxyhaemoglobin which further re duces the o...

Page 7: ...ning applianc es again until they have been checked and cleared for use by a competent person accord ing to national regulations Natural Gas is detected In the event of a Gas Alarm sounding and the ALARM GAS light being lit on the CHCO detec tor Fascia or the smell of gas even without an alarm Keep calm and carry out the following ac tions not necessarily in the order given extinguish all naked fl...

Page 8: ...ctivate an ancillary device such as a ven tilation fan or gas shut off valve Once triggered these devices may need to be manually reset but this should not be done until the source of carbon monoxide or fuel gas escape has been identified and the fault corrected 13 Maintenance This device should be tested periodically ideally every 6 months but a minimum of every 12 months The procedure is describ...

Page 9: ... RoHS and do not contain Lead Mercury Cadmium Hexavalent Chromium Chromium IV Polybrominated Biphenyls PBB Polybrominated Diphenyl Ethers PBDE GasTest Natural gas Mains Power Supply 230V AC within 2 of rating Volume Ratio of Gas Litres input up to 10 of L E L 3 Temperature 230C for the entire duration of the test 2 of rating Relative Humidity 45 for the entire duration of the test 10 Constant Baro...

Page 10: ... which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natural resources For more detailed information about recycling of this product please contact your local city office your house hold waste disposal service or the shop where you purchased the product Attention in some countries of the European Union the product is not i...

Reviews: