background image

S

afety 

F

irst 

U

SA, 

I

nc. 

3229 English Cove Lane, Marion, Iowa 52302-7608 

Phn 319-377-1129 • Fax 319-377-1539 • [email protected] 

 

Safety First USA Gas Detectors & Gas Valve Controller 

Scentry III-GFRAB 

Installation and Operating Instructions 

General Information 

 

Safety First USA’s Scentry III - GFRAB is a Gas Valve Controller that will keep ON a normally closed Gas valve. With the presence of an 

unsafe Level of Combustible gas, this gas valve controller will go into the alarm mode and shut-off one or more gas valves stopping the flow of gas

 
Location 

 

The gas valve controller should be placed the same as smoke detectors. You should install one gas valve controller for every 900 Square 

feet of space to be protected. In a very large room space the detectors on 25-foot centers. Locate the gas valve controller in areas where a gas leak and 
accumulation is most likely to occur. If the gas being used is Propane, butane or LP “ WHICH ARE HEAVER THAN AIR” the gas valve controller 
should be mounted 8”–12’ from the floor. If the gas being used is natural gas “ WHICH IS LIGHTER THAN AIR” the gas valve controller should be 
mounted 8”–12” from the ceiling. It is recommended that the gas valve be mounted on the out side of the building.

 

 
Installation 

 

Determine the proper size gas valve needed. Note the power requirements for this valve.  The gas valve controller can control valves up to 

24VA. Mount the gas valve controller at its optimum location. Plumb the gas valve.  Attach two 18awg wires from the gas valve to terminals 4 and 5 
on the gas valve controller’s 5 pin connector. 

 

Operation 

 

The Safety First USA Gas Valve Controller (GFRAB) will go into alarm mode at a 10% (LEL) lower explosive level. The alarm point of 

methane (natural gas) will vary from unit to unit, but be near this 10% level. After power has been on for two minutes the detector is ready to protect 
the home. A green LED should be on indicating power has been applied. Any time this LED changes to RED and the alarm goes to a BEEP- BEEP 
mode the gas Valve controller will drop out the gas valve and stop the flow of gas to the appliances being protected. The ONLY way to reset this unit 
is to remove the unburned fuel (vent the area that caused the alarm) and then push the red reset button. 

 
Testing the Installation 

 

The installation should always be tested. Use an 

un-lighted

 butane cigarette lighter and direct the gas to flow into the exposed sensor of the 

gas valve controller. In one or two seconds the gas valve controller will go into alarm and make a very loud BEEP – BEEP sound and shut off the gas 
valve being controlled. After 10 – 20 seconds the gas will clear and you can push the reset button. This will turn the gas valve back on. Pushing the 
RESET button is the ONLY way to reset this gas valve controller. 

 
Alarms should be taken seriously 

 

The  sensor  used  in  this  product  is  a  very  sensitive  chemical  sensor.  It  will  go  into  alarm  with  different  concentrations  of  different 

chemicals. Some of the chemicals that will cause an alarm in some concentrations. Alcohol, Butane, Gasoline, Hydrogen (from charging batteries), 
Kerosene, LP Gas, Propane, and Natural Gas (Methane).  
Take ANY Alarm Serious. 

TREAT ALL ALARMS AS POTENTIAL EMERGENCIES.

 

 
Limited Warranty 

 

The Safety First USA, Inc. GFRAB (Gas Valve Controller) is warranted to be free of defects in material and workmanship for a period of 

one (1) year from date of installation. If any component becomes defective during the warranty period, it will be replaced or repaired free of charge if 
the unit is returned postage prepaid to the factory. This warranty does not apply to any device that has been modified, changed or abused in any way. 
The  above  warranty  is  in  lieu  of  all  other  expressed  warranties,  obligations  or  liabilities.    THE  IMPLIED  WARRANTIES  OF 
MERCHANTABILITY  AND  FITNESS  FOR  PATICULAR  PURPOSE  ARE  LIMITED  TO  A  PERIOD  OF  ONE  YEAR  FROM  DATE  OF 
PURCHASE. Safety First USA, Inc shall not be liable for any incidental or consequential damages for breach of this or any other warranty expressed 
or implied arising out of or related to the use of this gas detector. Manufacturer or its agent’s liability shall be limited to replacement or repair as set 
forth above. Buyer’s sole and exclusive remedies are to return of the goods and repayment of the price, or repair and replacement of non-conforming 
goods or parts. 

 
Return Instructions 

 

Call 319-377-1129 and Request an (RMA) Return Material Authorization Number.  Enclose a written description of the problem you have 

experienced. Pack in a cardboard carton with at least two inches of packing on all sides. Return to the address below postage prepaid. 

 

04/20/12 

Reviews: