background image

Configuring the detector

How Many zones....?

The BX444 can be configured to provide one, two,
three or four zone protection. Sensors are enabled
and disabled by switching the zone select switches on

and off. To disable a zone move
the switch to the ON position. The

switches shown are in the zone
enabled position. When you have

made the switch change press the
reset on the BX444 fascia.

Gas or Carbon Monoxide...?

If the gas to be sensed is Explosive you must first
ensure that the correct sensor is connected to the
system. For instance, for Natural Gas SG590.  Each

pair of switches shown
below corresponds to a
sensor. From left to
right, 1 to 4.  To select

the Explosive Indication
on the fascia for a
particular sensor move
switch 1 to the ON

position and switch 2 to the off position. If another
zone is being used to sense carbon monoxide, again
ensure that the correct sensor is connected to that
zone for example CO200.

Pre-alarm adjustment

ppm/LEL & auto/ manual

reset selectors

Zone selectors

Explosive or Toxic

selectors

Terminal block 1

Terminal block 2

Continuous/pulsed main alarm

jumper

Printed Circuit board Layout

Select Toxic indication by moving switch 2 to the ON
position and switch 1 to the off position. In the above
picture this shows zone 1 Toxic, zone 2 explosive, zone 3
toxic, zone 4 explosive.

Pre-Alarm Sensitivity Adjustment

The  Pre-Alarm can be adjusted,  in the
case of Natural Gas or LPG, from 8%  to
15% of the Lower Explosive Level (LEL).
For Carbon Monoxide,  it can be adjusted
from 120ppm to 250ppm. Adjustment is
made using the pre-alarm potentiometer
marked PT1. To increase the sensitivity
turn the potentiometer away from the
central point either left or right. i.e. Central Position is 15%
LEL. Left or right 8% LEL.

Setting Main Alarm Memory function

The Main Alarm thresholds are not adjustable and are
fixed at  20% LEL for Natural Gas or LPG  and 300 ppm
for Carbon Monoxide. The main alarm can be configured
to provide  either a latching or an auto reset relay
actuation. For example  to turn off gas valves  or to boost
ventilation in car parks or areas containing carbon
monoxide. Should gas be sensed in boiler rooms
laboratories etc. the gas valve supplying the room will be
turned off by the detector. This must only be manually
reset following an alarm. However  if the BX444 is being
used to control the levels of carbon monoxide in car parks
as long as the ventilation is boosted and the levels of
Carbon Monoxide drop there is no requirement to
maintain the alarm so the unit can be allowed to
automatically reset.

Summary of Contents for BX444

Page 1: ...el of gas continues to rise then the main alarm relay is activated to either in the case of explosive gases break the electrical sup ply to the Safety Shut Off Valve or for CO sound a Gen eral Alarm to allow evacuation of the area Features The Pre Alarm can be adjusted in the case of Natu ral Gas or LPG from 8 to 15 of the Lower Ex plosive Level LEL For Carbon Monoxide it can be adjusted from 120p...

Page 2: ...ess to reset alarm This resets the detector memory 11 TEST Push button Provides full function test of detector 12 FAULT Flashes when the sensor is either faulty connected incorrectly or not selected 13 OVERLOAD Power consumption of the BX444 is too high 14 TOXIC Indicates that the Carbon Monoxide function is selected BX444 Facia 6 7 8 9 10 11 12 13 14 1 2 3 4 5 Digital Display This shows the quant...

Page 3: ...es above the room ambient may be experienced It is if possible better to mount the sensors on the opposite wall This is of course dependant on the size of the protected area Natural Gas is lighter than air and therefore will obviously rise therefore the SG590 methane sensor should be mounted 300mm from the ceiling of the protected area For LPG Propane and butane the SG590 LPG must be connected LPG...

Page 4: ... cables are routed through conduit or trunking containing other wiring the use of screened cable is advisable The wiring should be performed by a qualified person in accordance with current regulations Fig 4 Cable Entry Points The plug in terminal rail makes installation easy and quick Note It is essential that enough length is left in the cable loom to allow the facia to be hinged open as shown i...

Page 5: ... ON position and switch 1 to the off position In the above picture this shows zone 1 Toxic zone 2 explosive zone 3 toxic zone 4 explosive Pre Alarm Sensitivity Adjustment The Pre Alarm can be adjusted in the case of Natural Gas or LPG from 8 to 15 of the Lower Explosive Level LEL For Carbon Monoxide it can be adjusted from 120ppm to 250ppm Adjustment is made using the pre alarm potentiometer marke...

Page 6: ...of this gas detector Duomo will not be held responsible or liable This Gas detector is a safety device and therefore should only be maintained and installed by qualified persons To ensure correct function after installation Duomo provide a commissioning service using cali brated test gases For the service call 01905 797989 Warning To make the main alarm a latching operation move switch 1 shown to ...

Page 7: ...modes i Auto reset ii Latch with manual Reset When you have selected the correct memory function you must press the reset button so that this change takes effect The main alarm relay changes over the volt free relay and then with the Main Alarm light still on the relay re energises Check the position of the Jumper link JP1 This is located between the two terminal plugs When in the C position the r...

Page 8: ...upply 4 20mA output CO200 and 230 Catalytic Carbon Monoxide Gas Sensor with digital display and Change over Relay 30ppm CO IP55 Product Overview Gas Detection CO200A CO Sensor for Car Parks 12 or 24VDC supply 4 20mA Output IP55 Gas Safestart Guarantee This device is guaranteed for a period of 12 months from the date of purchase Conditions Substitution free of charge of any component recognized as ...

Reviews: