Troubleshooting

In case of alarm

Extinguish any naked flames.
Do not switch lights or electrical devices on or off.
Open all windows and doors to increase ventilation.
If the 'ALARM' LED is off the levels of gas have dropped. A responsible, qualified person is now safe to find the cause of
the alarm.
If the alarm sound remains constant, and the cause is not evident or possible to eliminate turn off the emergency
isolation valves to the area and contact your gas provider emergency line. They will advice accordingly.

If you are experiencing difficulties, having made the checks listed above call Duomo on 01905 797989 for
technical assistance.

The Problem

The Solution

No lights are illuminated on the fascia of the detector

Check that the electrical supply is reaching the
device and that the plug in terminal rail is pushed
into place.

The sensor fault light is illuminated

Sensor fault continues to alarm

The detector is subject to repeated alarms

The detector is in a main alarm condition and the
main gas valve is not closing

There is no supply to the solenoid valve

Check that the wiring is correct.

Check that the sensor wiring is correctly terminated
at both the sensor and detector. Check that 12V DC
is present at the sensor. The green light on the sensor
should be illuminated. Pressing the TEST button it is
possible to check the efficiency of the device and if
the sensors have been connected correctly.

Check that the connections are correct and that
power is supplied to the valve i.e. the valve is not
stuck in the open position. The function of the alarm
relays both Pre-Alarm and Main Alarm can be
checked by pressing the TEST button on the detector
fascia. Check that the main alarm action is configured
for a latching alarm (see setting on internal menu).

Check the sensor wiring. If the red Overload LED is lit
a short circuit or overload has occurred on the sensor
or the connecting cable.

Ensure that there is not an occassional gas leak. This
may be due to a valve or joint which leaks under
pressure.

The Main Alarm relay is a volt-free contact, therefore
you must connect the live supply to the common of
the main alarm relay contacts. Check the wiring
diagram in this manual.

Sensor is connected, but no information is shown on
the display.

Check that the sensor is enabled in the internal
menu.

w:

www.duomo.co.uk

-

e:

[email protected]

-

t:

01905 797989

-

f:

01905 774296

|

©

Duomo (UK) Ltd. 2007

Summary of Contents for BX216

Page 1: ...story The BX216 has five main terminal blocks for the following The incoming mains supply The alarm circuit wiring including fault siren pre alarm and main alarm relays The power supply to the sensors The 4 20mA return cable from the sensors A 0 10V output to BMS proportional to the 4 20mA return signal The front panel has an LCD display showing the date time current sensor levels and much more LE...

Page 2: ...mming menus 12 Printer Port Allows a printer to be attached to print off all the data stored in memory 13 Test Button This button simulates a gas leak and tests the full funcionality of the BX216 14 Reset Button When pressed it resets all internal memory 15 Output Terminal Block Converts the 4 20mA return signal from the sensors to a 0 10V output connection for BMS 16 Sensor Return Terminal Block ...

Page 3: ... ZONE 2 NC NC NO NO C NC NO C NC NO C C 3 5A Power Supply 230V 14 13 NC NO C NC NO C Relay outputs 2 1 3 12 11 10 9 8 7 6 5 4 FAULT RELAY SIREN RELAY PRE ALARM ZONE 1 MAIN ALARM ZONE 1 MAIN ALARM ZONE 2 PRE ALARM ZONE 2 NC NC NO NO C NC NO C NC NO C C 3 5A Power Supply 230V 14 13 NC NO C NC NO C Relay outputs 2 1 3 12 11 10 9 8 7 6 5 4 FAULT RELAY SIREN RELAY PRE ALARM ZONE 1 MAIN ALARM ZONE 1 MAI...

Page 4: ...ne is displayed for 8 seconds in turn To cycle through the zones use the left and right keys on the keypad To pause on a zone press the Enter key Press the Enter again to move on and continue cycling through The sensors must be mounted as shown below with the sintered head pointing vertically down When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrate...

Page 5: ...s 1234567812345678 Zone 1 Zone 2 TExxxxxx 12345678 xxxxxxxx 12345678 T been set to detect toxic gas i e carbon monoxide An means it has been set to detect explosive gas i e methane Once you have set each zone up move down to the and press Enter This will move you into the next screen that allows you to set the pre alarm level for each sensor Note If no sensor is attached to a particular zone you w...

Page 6: ...eters for each option are as follows Controls how the main alarm relay operates in an alarm condition Continuous means the relay will remain activated after the alarm has passed Impulse means the relay will activate for 20 seconds and then revert back to its normal state Moving the cursor down to the and pressing Enter will move you down to the next screen shown below To go back to the top menu pr...

Page 7: ...nsor Blackout Power to the BX216 has been lost Check incoming 230V power supply Reset The BX216 has been reset using the button on the fascia following an alarm condition Low Battery The backup battery not supplied is running low Probe Enabled The sensor indicated has been enabled using the internal setup Prove Disabled The sensor indicated has been disabled using the internal setup Hard Reset The...

Page 8: ...onfigured this will remain on until the RESET button is pressed 5 In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas The maximum concentrations are 40 LEL for methane in air 350ppm for carbon monoxide 0 85 MOL for propane Any higher than this can reduce sensor life NOTE NEVER TEST USING NEAT GAS THIS WILL POISON THE SENSOR 6 To simulate a sensor...

Page 9: ...orrect Check that the sensor wiring is correctly terminated at both the sensor and detector Check that 12V DC is present at the sensor The green light on the sensor should be illuminated Pressing the TEST button it is possible to check the efficiency of the device and if the sensors have been connected correctly Check that the connections are correct and that power is supplied to the valve i e the...

Page 10: ...ation No of remote sensors 16 No of selectable zones 2 Monitored gas indication Through illuminated display Input signal 4 20mA Device precision 1 FS Reaction time 2 seconds Working temperature 10 C to 45 C Start up self diagnostic delay 90 seconds Suitable for use with sensor type SGM595 CO100Ar CO200A SG895 Maximum distance for sensor connection 100m Cable diameter for sensors 1mm2 CSA Dimemsion...

Reviews: