BX216 operation

Maintenance procedure

This detector must be function checked as described above using calibrated test gas every 6 months. To arrange for a
Duomo engineer to conduct this work or to arrange a service contract please call 01905 797989.

Before powering up the BX216 once again check that all electrical connections are correct.

1. Apply 230V supply to the Ph and N terminals. Ensure that the correct fuse is used in the supply. (3 or 5A max.)

2. All of the lights on the fascia will light up in turn. This will take approximately 20 seconds. This checks the function of

all the LED's.

3. The ON LED will remain flashing for about 90 seconds. This is the sensor warm-up period. The gas detector will not

provide gas detection during this period. When the ON light becomes constant the detector is in operation.

4. By pushing and maintaining pressure on the manual TEST button a function test can be performed for all pre-alarm

relays and main alarm relay, together with LED's and audible alarm.

The sequence will be:

a) The pre-alarm threshold (user selected) and Pre-Alarm 1 LED will be actuated. The Pre-Alarm 1 relay

will be changed over.

b) The 20% LEL / 300

ppm

and Main Alarm LED will be actuated. The Main Alarm relay will be changed over. The

relevant Alarm LED's will light to show which zones are in alarm.

By releasing the the manual TEST button the lights will go out and the audible alarm will cease. If a latched alarm function
on the main relay is configured this will remain on until the RESET button is pressed.

5. In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas. The maximum

concentrations are;

- 40% LEL for methane in air
- 350

ppm

for carbon monoxide

- 0.85% (MOL) for propane

Any higher than this can reduce sensor life. NOTE: NEVER TEST USING NEAT GAS. THIS WILL POISON THE SENSOR.

6. To simulate a sensor fault situation disconnect the sensor plug. The detector will go into a FAULT alarm and the sensor

fault relay will be actuated.

Commissioning

It is strongly recommended that this detector should be commissioned by Duomo Commissioning Engineers or
engineers approved by Duomo to carry out this work. A quotation for commissioning or service will be provided upon
request. Fax site details and preferred date for commissioning to 01905 774296 and the Duomo Service Department will
fax back confirmation.

The benefits of this equipment being commissioned by Duomo are:

On board spares. If for whatever reason this equipment doesn't function correctly Duomo engineers will have spares on
board to ensure that the commissioning is successful.

A Duomo Commissioning Certificate is provided.

It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the
detector so that the Duomo Engineer is the first to power up the unit on site. This allows wiring to be checked prior to
commissioning and avoids damage due to incorrect connection. Guarantees for this product will become void if damage
is caused by the installer.

w:

www.duomo.co.uk

-

e:

[email protected]

-

t:

01905 797989

-

f:

01905 774296

|

©

Duomo (UK) Ltd. 2007

Summary of Contents for BX216

Page 1: ...story The BX216 has five main terminal blocks for the following The incoming mains supply The alarm circuit wiring including fault siren pre alarm and main alarm relays The power supply to the sensors The 4 20mA return cable from the sensors A 0 10V output to BMS proportional to the 4 20mA return signal The front panel has an LCD display showing the date time current sensor levels and much more LE...

Page 2: ...mming menus 12 Printer Port Allows a printer to be attached to print off all the data stored in memory 13 Test Button This button simulates a gas leak and tests the full funcionality of the BX216 14 Reset Button When pressed it resets all internal memory 15 Output Terminal Block Converts the 4 20mA return signal from the sensors to a 0 10V output connection for BMS 16 Sensor Return Terminal Block ...

Page 3: ... ZONE 2 NC NC NO NO C NC NO C NC NO C C 3 5A Power Supply 230V 14 13 NC NO C NC NO C Relay outputs 2 1 3 12 11 10 9 8 7 6 5 4 FAULT RELAY SIREN RELAY PRE ALARM ZONE 1 MAIN ALARM ZONE 1 MAIN ALARM ZONE 2 PRE ALARM ZONE 2 NC NC NO NO C NC NO C NC NO C C 3 5A Power Supply 230V 14 13 NC NO C NC NO C Relay outputs 2 1 3 12 11 10 9 8 7 6 5 4 FAULT RELAY SIREN RELAY PRE ALARM ZONE 1 MAIN ALARM ZONE 1 MAI...

Page 4: ...ne is displayed for 8 seconds in turn To cycle through the zones use the left and right keys on the keypad To pause on a zone press the Enter key Press the Enter again to move on and continue cycling through The sensors must be mounted as shown below with the sintered head pointing vertically down When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrate...

Page 5: ...s 1234567812345678 Zone 1 Zone 2 TExxxxxx 12345678 xxxxxxxx 12345678 T been set to detect toxic gas i e carbon monoxide An means it has been set to detect explosive gas i e methane Once you have set each zone up move down to the and press Enter This will move you into the next screen that allows you to set the pre alarm level for each sensor Note If no sensor is attached to a particular zone you w...

Page 6: ...eters for each option are as follows Controls how the main alarm relay operates in an alarm condition Continuous means the relay will remain activated after the alarm has passed Impulse means the relay will activate for 20 seconds and then revert back to its normal state Moving the cursor down to the and pressing Enter will move you down to the next screen shown below To go back to the top menu pr...

Page 7: ...nsor Blackout Power to the BX216 has been lost Check incoming 230V power supply Reset The BX216 has been reset using the button on the fascia following an alarm condition Low Battery The backup battery not supplied is running low Probe Enabled The sensor indicated has been enabled using the internal setup Prove Disabled The sensor indicated has been disabled using the internal setup Hard Reset The...

Page 8: ...onfigured this will remain on until the RESET button is pressed 5 In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas The maximum concentrations are 40 LEL for methane in air 350ppm for carbon monoxide 0 85 MOL for propane Any higher than this can reduce sensor life NOTE NEVER TEST USING NEAT GAS THIS WILL POISON THE SENSOR 6 To simulate a sensor...

Page 9: ...orrect Check that the sensor wiring is correctly terminated at both the sensor and detector Check that 12V DC is present at the sensor The green light on the sensor should be illuminated Pressing the TEST button it is possible to check the efficiency of the device and if the sensors have been connected correctly Check that the connections are correct and that power is supplied to the valve i e the...

Page 10: ...ation No of remote sensors 16 No of selectable zones 2 Monitored gas indication Through illuminated display Input signal 4 20mA Device precision 1 FS Reaction time 2 seconds Working temperature 10 C to 45 C Start up self diagnostic delay 90 seconds Suitable for use with sensor type SGM595 CO100Ar CO200A SG895 Maximum distance for sensor connection 100m Cable diameter for sensors 1mm2 CSA Dimemsion...