Typical Wiring Schematic for BX116

Electrical Installation

Installing A Sensor

The BX116 is a safety device designed to give audible
alarms and automatically provide latched electrical
isolation of associated gas safety shut off valves in the
event of a gas leak or build up of toxic gases. The sensor
can be located up to 100m from the gas detector. Cable
size should be 1mm2 CSA. If the sensor cables are run
seperately in specific conduit it is not essential to use
screened cable but if the cables are routed through
conduit or trunking containing other wiring the use of
screened cable is advisable. The wiring should be
performed by a qualified person in accordance with
current regulations. The plug-in terminal rail makes
installation easy and quick. Do not mount close to any
heat source or in an area where moisture is likely to effect
operation. The IP rating of this unit is IP44. Sensors should
be positioned as shown below. If you require any
guidance on this please call our technical help on 01905
797989.

The sensors must be mounted as shown below with the
sintered head pointing vertically down. When replacing
sensors never seperate a sensing head from its PCB. The
sensor will have been calibrated using this particular
board and therefore will not function correctly with any
other.

Important Notes

Always check the wiring before powering up the
system.

Do not test this sensor with anything other than
Duomo test gas (see

'BX116 Operation'

section for

further information). Concentrations above this will
damage the sensor and shorten sensor life. The
installation of this gas detector does not release the
user from observing all the regulations concerning the
characteristics, installation and and the use of gas
appliances; the ventilation of the environment and the
elimination of combustion products in accordance with
the local recommendations, regulations and bylaws. For
any damage caused to people, property or animals
resulting from incorrect connection, installation or
application of this gas detector Duomo will not be held
responsible or liable. To ensure correct function after
installation Duomo provide a commissioning service
using calibrated test gases. For this service call 01905
797989.

SGM595

autosetting

ON

SGM595

autosetting

ON

SGM595

aut

osetting

ON

300

1600

300

Natural

Gas

Carbon

Monoxide

L.P.G

.

Note: Connections for other detectors may differ. Check detector datasheet wiring schematic. 1mm

2

CSA cable only

Mains power

supply

Relay outputs

2

1

3

2

1

3

8

7

6

5

4

2

1

3

8

7

6

5

4

Return cables from sensors

ZONE 2

ZONE 1

ZONE 2

ZONE 1

Power supply

to sensors

2

1

3

2

1

3

12

11

10

9

8

7

6

5

4

FAULT
RELAY

PRE-

ALARM
ZONE 1

MAIN

ALARM
ZONE 1

MAIN

ALARM
ZONE 2

PRE-

ALARM
ZONE 2

NC

NC

NC

NO

NO

NO

C

NC

NO

C

C

NC

NO

C

C

3/5A

Power

Supply 230V

AC

N

Ph

Summary of Contents for BX116

Page 1: ...ly and alarm circuit wiring and the second is for connecting the sensor wiring This reduces the chance of incorrect site wiring The front panel has two banks of eight lights indicating in rotation which probe is currently monitoring and a bright display showing the LEL or PPM gas concentration measured Operation When the remote sensor detects the presence of the target gas a 4 20mA signal is sent ...

Page 2: ...ated 11 Main Alarm Zone 2 20 L E L concentration of gas detected in Zone 2 Main alarm relay actuated 12 LEL L E D This lights when the jumper switch for display data is set to read in lower explosive limit LEL 13 Zone 2 Indication These L E D s represent the Zone 2 sensors and flash when a sensor is connected 14 No of Sensors Switches DIP switches allowing you to select how many sensors can be att...

Page 3: ...ed using this particular board and therefore will not function correctly with any other Important Notes Always check the wiring before powering up the system Do not test this sensor with anything other than Duomo test gas see BX116 Operation section for further information Concentrations above this will damage the sensor and shorten sensor life The installation of this gas detector does not releas...

Page 4: ...play units The BX116 can display the current gas concentration detected in either LEL or ppm This is done by closing one of two jumpers on the PCB on the rear of the door of the unit Closing the upper jumper sets the unit to LEL Closing the lower jumper sets the unit to ppm Disabling or uninstalling sensors The BX116 can accept up to 16 sensors divided into two zones You should deselect the DIP sw...

Page 5: ...be performed for all pre alarm relays and main alarm relay together with L E D s and audible alarm The sequence will be a The 8 L E L 120ppm and Pre Alarm 1 L E D will be actuated The Pre Alarm 1 relay will be changed over b The 20 L E L 300ppm and Main Alarm L E D will be actuated The Main Alarm relay will be changed over The relevant Alarm L E D s will light to show which zones are in alarm By r...

Page 6: ...tion and the main gas valve is not closing There is no supply to the solenoid valve Check that the plug is inserted correctlty Check that the sensor wiring is correctly terminated at both the sensor and detector Check that 12V DC is present at the sensor The green light on the sensor should be illuminated Pressing the TEST button it is possible to check the efficiency of the device and if the sens...

Page 7: ...for this product will become void if damage is caused by the installer Technical specification Power Supply 230V AC 50Hz 10 Secondary Battery 12V DC 10 Power Consumption 30W maximum 230V Power Consumption 25W maximum 12V Relay contact range 10A 230V resistive 5A 30V DC resistive 1st pre alarm Can be set from 8 L E L 120ppm to 13 250ppm of LEL Main alarm Fixed at 20 L E L 300ppm Sensor fault Short ...

Reviews: