3.0 OPERATION
When the compressor is given a "hold"
command, valve A is de-energized (closed) and
slide valve movement is halted. The internal
pressure regulating valve allows oil to bleed from
the slide valve chamber during the hold
condition. If valve B is then de-energized (open),
the high pressure oil acting on the slide valve
will be vented to suction, and the pressure in the
slide valve chamber will be reduced. The slide
valve spring will now move the slide valve back
toward the minimum capacity position.
Under standard conditions, the compressor will
load in 60 seconds and unload in 55 seconds.
SLIDE VALVE POSITION
UNLOADING
LOADING
HOLD
SOLENOID VALVE A
(NORMALLY CLOSED)
CLOSED
(DE-ENERGIZED)
OPEN
(ENERGIZED)
CLOSED
(DE-ENERGIZED)
SOLENOID VALVE B
(NORMALLY OPENED)
OPEN
(DE-ENERGIZED)
CLOSED
(ENERGIZED)
CLOSED
(ENERGIZED)
FIGURE 3.13
COMPRESSOR CAPACITY CONTROL DETAIL
- 18 -
Summary of Contents for ACXi 165-5SP-LN
Page 6: ...2 0 INSTALLATION FIGURE 2 3 2 ACXi 165 5SP LN TYPICAL RIGGING 6...
Page 14: ...3 0 OPERATION FIGURE 3 2 ACXi 165 5SP LN TYPICAL SCHEMATIC PIPING 14...
Page 20: ...CHECKED REV NO DATE APPROV 4 0 ELECTRICAL FIGURE 4 2 ACXi 165 5SP LN WIRING SCHEMATIC 20...
Page 21: ...4 0 ELECTRICAL 21...
Page 22: ...4 0 ELECTRICAL 22...
Page 23: ...4 0 ELECTRICAL 23...
Page 24: ...4 0 ELECTRICAL 24...
Page 25: ...4 0 ELECTRICAL 25...
Page 26: ...4 0 ELECTRICAL 26...
Page 27: ...4 0 ELECTRICAL 27...
Page 28: ...4 0 ELECTRICAL 28...
Page 29: ...4 0 ELECTRICAL 29...
Page 30: ...4 0 ELECTRICAL 30...
Page 31: ...4 0 ELECTRICAL 31...