background image

3.0 OPERATION

2. Start compressor(s), check the gages and note

if the pressures are within the prescribed
limits.

3. Check the refrigerant sight glass at the TX

Valve to be sure it is free of bubbles. If not,
charge as required to clean sight glass.

4. Stage unit down until all compressors are off

and check the compressor crankcase sight
glass for oil level. It should be 1/2 to 3/4 of
the compressor sight glass.

5. Restart the compressor. After an hour of

operation, the expansion valve superheat
setting should be checked, it should be
between 9° and 12°F at full load design
conditions. In some instances, it will be
necessary to lower the superheat setting to
ensure proper distribution. Turn the TX valve
adjustment stem clockwise to increase the
superheat setting and counterclockwise to
decrease the setting. Be sure and allow ample
time between each adjustment for the system
to rebalance.

6. The electrical control settings should be

checked and if necessary, reset to those
settings indicated on the wiring diagram.
Safety controls are factory set and must be
maintained at settings indicated on the wiring
diagram.

7. The temperatures of the chilled water both in

and out, should be checked to insure the unit
is operating within the desired temperatures.

3.6 SHUT-DOWN 

(OVERNIGHT

OR WEEKEND)

To shut-down in the unit with compressors on or
off, turn each individual compressor switch. Do
not close any valve. The chilled water pump may
then be turn off. If it is possible that the
overnight ambient will drop below 65°F, it is
preferable to leave the chilled water pump on.
Finally, do not open the main unit disconnect.
Main power is required to keep the sump heaters.

3.7 SEASONAL SHUT-DOWN

PROCEDURE

Standard Ambient Units
1. Follow standard overnight 

shut-down

procedure

2. Turn off chilled water pump
3. Close manual discharge valve
4. Close liquid valve on sealpot
5. If ambient temperature during the extended

shut-down period will not get below freezing,
the chilled water system may be left filled, If
the ambient temperature will be below
freezing, drain all water thoroughly, removing
all vent & drain plugs from both heads of the
evaporator, and blow out tubes will
compressed air to avoid serious stagnant
water corrosion.

6. Finally, it is recommended that an oil sample

be taken from each compressor & submitted
for lab analysis.  Dunham-Bush offers this
service in its "Oil  Kare" program. This
analysis should be done at the end of each
operating season or every 6 months if the unit
is used year round.
The power supply to the unit may be de-
energized to conserve energy. Just remember
that all heaters will now be inactive, and the
evaporator could freeze-up if not properly
drained.

3.8 SEASONAL START-UP

PROCEDURE

l. Check fan drives for wear, rust, propeller

clearance, etc. and make necessary repairs &
adjustments. Grease main fan shaft bearings
with a good grade of EP ball bearing grease.

2. Check & clean condenser fin surface if

necessary. Use a warm water soap solution,
being careful not to bend fins. Comb out bent
fin areas.

3. Check all power supply connections at all

points, and all control terminal screws for
tightness.

4. Energize main power to unit & leave on for at

least 24 hours in order for compressor to
thoroughly warm up.

5. Start chilled water pump and verify correct

flow-rate glycol % if required. Bleed-off
system air if necessary.

6. Open main discharge valve in discharge

header.

7. Open liquid valve on sealpot.

- 16 -

Summary of Contents for ACXi 165-5SP-LN

Page 1: ...tal Ankara Turkey AIR COOLED ROTARY SCREW CHILLERS INSTALLATION OPERATION AND MAINTENANCE MANUAL INSTALLATION OPERATION AND MAINTENANCE MANUAL MODEL ACXi 165 5SP LN 50 Hz 50 Hz 50 Hz Products That Per...

Page 2: ...r 35 4 5 4 Load Control Microcomputer 35 4 5 5 Ramp Control Microcomputer 35 4 5 6 Current Limiting Microcomputer 36 4 5 7 Staging Control Microcomputer 36 4 5 8 Manual lead Lag Control Microcomputer...

Page 3: ...under a careful quality control system If the package is installed operated and maintained with care and attention to the instructions contained herein it will give many years of satisfactory service...

Page 4: ...PD ft wg 402 4 19 8 Min Max Water Flow GPM 197 5 481 6 Min Max Water Flow PD ft wg 6 1 30 0 Air Cooled Condenser Coil Rows Deep FA Sq Ft 3 141 2 3 141 2 No Of Fans 6 6 Fan Diameter inch mm 31 5 800 0...

Page 5: ...portant that the following inspection be completed in the presence of the carrier s representative 1 Check all crates and cartons received against the Bill of Lading Shipping Papers to be sure they ag...

Page 6: ...2 0 INSTALLATION FIGURE 2 3 2 ACXi 165 5SP LN TYPICAL RIGGING 6...

Page 7: ...e located in the vicinity of steam hot air or fume exhausts Another consideration which must be taken into account is that the unit should be mounted away from noise sensitive spaces and must have ade...

Page 8: ...oted 2 Pit Installations Are Not Recommended Re Circulation Of Hot Condenser Air In Combination With Surface Air Turbulence Cannot Be Predicted Hot Air Re Circulation Will Severely Affect Unit Efficie...

Page 9: ...2 0 INSTALLATION FIGURE 2 4 2 ACXi 165 5SP LN DIMENSIONAL DATA NOTE ALL DIMENSIONS ARE IN INCHES MM 9...

Page 10: ...evaporator heads Cut piping holes in the removable access panel at the end of the unit Opening the hole to the left hand side of the panel so that it can still be removed after piping is in place Hole...

Page 11: ...el Dimensions Inches A Dim B Dim C Dim D Dim E Dim ACXi 165 5SP LN 86 18 141 3 4 141 3 4 21 FIGURE 2 5B ACXI 165 5SP LN ISOLATOR POINT LOAD DATA Unit Model Point Load LBS Total Operating Pos 1 Pos 2 P...

Page 12: ...controls must be set to factory recommendations 2 10 REQUEST FOR START UP REPRESENTATIVE After the installation has been completed and checked Form 9180 must be filled out and sent to the Dunham Bush...

Page 13: ...before attempting to start Important Do not use chilled water pump operation via the flow switch or Aux chilled water pump contacts to start stop this unit These are safety controls not operational co...

Page 14: ...3 0 OPERATION FIGURE 3 2 ACXi 165 5SP LN TYPICAL SCHEMATIC PIPING 14...

Page 15: ...1 10 100 100 1000 FLOW RATE USGPM PRESSURE DROP FT WG 3 0 OPERATION FIGURE 3 3 EVAPORATOR WATER PRESSURE DROP ACXi 165 5SP LN 15...

Page 16: ...nnect Main power is required to keep the sump heaters 3 7 SEASONAL SHUT DOWN PROCEDURE Standard Ambient Units 1 Follow standard overnight shut down procedure 2 Turn off chilled water pump 3 Close manu...

Page 17: ...from the boiling refrigerant flows up the suction pipes through shut off valves suction check valves and suction filters inside compressor into compressors where it is compressed and starts the cycle...

Page 18: ...energized open the high pressure oil acting on the slide valve will be vented to suction and the pressure in the slide valve chamber will be reduced The slide valve spring will now move the slide valv...

Page 19: ...fety conditions satisfied Leaving chilled water temperature 2 F or more above setpoint A compressor is started by first energizing 1M1 followed by 1M2 Anti recycle time of 15 minutes is initiated with...

Page 20: ...CHECKED REV NO DATE APPROV 4 0 ELECTRICAL FIGURE 4 2 ACXi 165 5SP LN WIRING SCHEMATIC 20...

Page 21: ...4 0 ELECTRICAL 21...

Page 22: ...4 0 ELECTRICAL 22...

Page 23: ...4 0 ELECTRICAL 23...

Page 24: ...4 0 ELECTRICAL 24...

Page 25: ...4 0 ELECTRICAL 25...

Page 26: ...4 0 ELECTRICAL 26...

Page 27: ...4 0 ELECTRICAL 27...

Page 28: ...4 0 ELECTRICAL 28...

Page 29: ...4 0 ELECTRICAL 29...

Page 30: ...4 0 ELECTRICAL 30...

Page 31: ...4 0 ELECTRICAL 31...

Page 32: ...e viewed with the right and left arrow keys NOTE When displaying analog sensors the PAGE MODE key can be pressed to display two new analog inputs after each arrow key is pressed Press PAGE MODE again...

Page 33: ...0 3 psig with a zero calibration of 1 then new calibration would be 58 60 3 1 3 3 3 So the zero calibration should be changed to 3 Then the computer will display 58 3 4 4 7 TO SET DATE AND TIME 1 You...

Page 34: ...le press the right arrow key and repeat steps 7 13 15 To delete a schedule clear all of the days by pressing 0 at Step 12 The schedule group turns on when any of the individual schedules turns on The...

Page 35: ...al load The load target is varied based on rate of approach to desired temperature preventing significant temperature oscillations The current limit function see Section 4 5 7 overrides the temperatur...

Page 36: ...Microcomputer On multi compressor machines the lead compressor can be chosen by storing 0 0 or 1 0 in the lead setpoint B position 0 0 is for lead on compressor 1 and 1 0 is for lead on compressor 2 i...

Page 37: ...unning Its purpose is to prevent refrigerant migration into the oil during shut down For this reason it is essential that heaters be energized for 24 hours before starting a compressor 4 6 SAFETY FUNC...

Page 38: ...y lCR will de energize and open the control circuit A LED light located on the PCR indicates a good voltage supply The power loss A setpoint is factory set to 0 0 to allow automatic start after PCR fa...

Page 39: ...load performance data on the log sheet The best measure of performance of evaporator is approach which is the difference between leaving water temperature and saturated refrigerant temperature at the...

Page 40: ...34 06 36 70 130 0 896 6 58 85 14 92 69 14 20 63 16 0 110 3 43 56 41 98 30 90 34 94 140 0 965 5 63 50 17 50 73 65 23 14 18 0 124 1 38 99 39 44 26 43 32 46 150 0 1034 5 67 90 19 94 77 92 25 51 20 0 137...

Page 41: ...ble at any operating condition the circuit is short of charge Be careful not to overcharge the machine Overcharging will result in considerable liquid logging in the condenser and excessive condensing...

Page 42: ...Check wiring against drawing 4 Compressor overload a Compressor drawing high amps a Check motormegohms Reset overloads run com presssor an check amps Do not exceed RL x 1 25 Call D B serviceman 5 High...

Page 43: ...ORATOR WATER TEMPERATURE IN EVAPORATOR WATER TEMPERATURE OUT EVAPORATOR PRESSURE DROP PSI IN WATER EVAPORATOR WATER FLOW GPM CONDENSER AIR TEMPERATURE IN AMBIENT AC ONLY 1 2 3 ACTUAL VOLTAGE COMPRESSO...

Reviews: