10 Error overview
MPA 51xx
Error
ID
Internal
error
Error description
Possible cause of the error
0x4C
ERROR_PARAMETER_RECORD_STICK_
BLOCK_ADJUSTMENT
? A parameter could not be copied from
the stick, for ex. because the variable lim-
its in the MPA were confined.
0x4d
ERROR_PARAMETER_RECORD_STICK_IN-
CORRECT_PASSWORD
? The entered password is not suitable for
this stick
0x4E
ERROR_PARAMETER_RECORD_STICK_
NO_CONTINUOUS_RUN
? Duration of the standard mode (P70) is
higher than 23 h 59 min and the continu-
ous run is not enabled
0x4F
ERROR_PARAMETER_RECORD_STICK_
TYPE
? The stick does not fit with the type of au-
tomatic burner control
0x50
●
ERROR_FEEDBACK_ADDITION_INCORRECT
0x51
ERROR_ADDITION_INVALID_DELAY
? Parameter P52 or P53 are set to an
invalid value because the concerned state
(P50 or P51) cannot have the set duration
0x52
not used
0x53
ERROR_LACKOFGAS_GDWVPS
0x54
●
ERROR_PWM_CALIBRATION_VALUES
? The EEPROM was changed or deleted
when programming the parameter record
stick
? Parameter record stick defective
0x55
●
ERROR_PARAMETER_RECORD_STICK_
CRC_DATA
? Parameter record stick defective
...
not used
10.4 Error from the application (from 0xA0)
0xA0
ERROR_STATE_DURATION_TOO_LONG
(Error fan and/or stepped motor)
? in the state 3, 16 and 23: The fan and/or
the stepped motor cannot reach its nomi-
nal value within the expected time period
? other states: Internal error
0xA1
ERROR_FAN_STARTUP
(Error fan and/or stepped motor)
? in the state 3, 16 and 23: The fan and/or
the stepped motor cannot reach its nomi-
nal value within the expected time period
? other states: Internal error
0xA2
ERROR_SAFETY_CHAIN_OPEN
? The safety chain has been opened or is
not closed
? The wires of the safety chain are inter-
rupted
0xA3
ERROR_PARAMETER_RECORD_STICK_
NO_PASSWORD
? The values in the MPA and in the param-
eter record stick are different. The request-
ed password was not entered (timeout).
0xA4
●
ERROR_FEEDBACK_V1_INCORRECT
0xA5
●
ERROR_FEEDBACK_V2_INCORRECT
0xA6
ERROR_EXTERNAL_LIGHT
? Earth connection to an ionisation elec-
trode
? Gas flows out and is burned for ex. by
neighbouring burners
? Connected flame detector detects ex-
ternal light