![Dungs MPA 5111 Manual Download Page 41](http://html1.mh-extra.com/html/dungs/mpa-5111/mpa-5111_manual_2539651041.webp)
41 … 68
40 … 68
Printed in German
y • Edition 02.14 • Nr
. 254 722
10 Error overview
MPA 51xx
Error
ID
Internal
error
Error description
Possible cause of the error
0x19
●
not used
0x1A
●
ERROR_SWWD_DURING_INITIALISATION
0x1B
●
ERROR_BUFFEROVERFLOW
0x1C
●
ERROR_SYNCHRONISATION_DURING_INI-
TIALISATION
0x1D
●
ERROR_PROCESSORFAILURE
? MPA is influenced by strong EMC inter-
ferences
0x1E
●
ERROR_SFRREGISTER_STATEBLOCK
...
not used
10.3 Error from the extended functions (0x40 to 0x9F)
0x40
ERROR_FANDEFAULTS
? In the curve segment, a fan default is
predefined, which is smaller than the mini-
mum speed or higher than the maximum
speed of the fan (P26 or P27).
P26 (min. speed) is 500 U/min but the
speed for modulation degree 0% is set
to 480 rpm. Or P27 (max. speed) is set to
5600 rpm but the pre-aeration B should be
carried out with 5800 rpm.
0x41
ERROR_FAN_DEVIATION
? The number of pulses in the fan feed-
back is set to an incorrect value
? The fan is not suitable for the desired
speed
? The predefined tolerance is too low or
the fan controller is not optimised
0x42
ERROR_FAN_NO_FEEDBACK
? The feedback line of the fan is not cor-
rectly connected or is interrupted
? The fan is blocked and does not work
? The fan is not supplied with power or is
defective
0x43
ERROR_TEST_IONISATIONINPUT
0x44
ERROR_CURVECRC16_TEST
? The curve segment was temporarily
changed, for ex. for putting the MPA into
operation, and was not correctly enabled
later
0x45
●
ERROR_INVALID_MODULATIONDEGREE
? Modulation degree is outside the limits
0x46
not used
0x47
●
ERROR_INVALID_STEPPEDMOTORTYPE
? Check stepped motor (compare P30)
0x48
ERROR_STEPPEDMOTOR_TOLERANCE_EX-
CEEDED
? The lines to the stepped motor are not
correctly connected or partly interrupted
? The stepped motor is charged with more
than the admissible torque, for example
due to improper mounting of the flap or
pressure impulses.
0x49
ERROR_STEPPEDMOTOR_REFERENCE_
NOT_FOUND
? see error 0x48
0x4A
ERROR_STEPPEDMOTOR_NO_REACTION
? see error 0x48
0x4b
ERROR_PARAMETERRECORDSTICK_NOT_
FOUND
? Parameter record activated but not
plugged in the MPA
? Stick defective
? Duration of the standard mode (P70) is
higher than 23 h 59 min and the continu-
ous run is not enabled
? PWM outputs configured to analogue
operation (0..10 V or 4...20 mA) but no suit-
able stick is plugged in.