17
Substitution of spray cans
After a nebulisation or at least every three years (even if no nebulisation) it’s necessary to substitute the
spray cans (the expiry date is stated on the bottom of the container).
FOLLOW STRICTLY AND IN PRECISE ORDER THE FOLLOWING INSTALLATION
INSTRUCTIONS, OTHERWISE MAY RESULT AN ACCIDENTAL NEBULISATION OF
HARMFUL GAS
After a nebulisation:
1.
Deactivate the control panel (
IN1
and
IN2
to +12 V
) with tamper control excluded, then
remove the cover of Peperosso
2.
Enable Peperosso removing the po12 V
from
IN1
3.
Press the
K1
button to bring the plunger to rest
4.
Block Peperosso giving the po12 V
to
IN1
5.
Unplug the
CN2
connector which power the motor, in this way the plunger is mechanically
blocked
6.
Substitute the spray cans
7.
Plug in the
CN2
motor connector
8.
Close the cover
Substitution for maintenance:
1.
Deactivate the control panel (
IN1
and
IN2
to +12 V
) with tamper control excluded, then
remove the cover of Peperosso
2.
Block Peperosso giving the po12 V
to
IN1
3.
Unplug the
CN2
connector which power the motor, in this way the plunger is mechanically
blocked
4.
Substitute the spray cans
5.
Plug in the
CN2
motor connector
6.
Close the cover