Meaning of the LEDs on front panel

A small USB connector for the connection of ModGSMIII to 
the PC is located on the front panel. The red LED located 
on   the   top   of   this   connector   reports   the   communication 
activity  between the PC and the module itself. During the 
communication this LED will flash showing the information 
exchange.

In addition to this USB communication LED, the following 
ones are placed on the front panel:

LED Init

LED Field  

  

LED SMS IN

LED SMS OUT

LED Power (ON)

The following table shows the possible combinations of the 
LEDs signalling. Fourteen different situations can be identi-
fied   as   listed   in   the   following   table.   “

FF

”   means   “

Fast 

Flash

”, while “

SF

” means “

Slow Flash

”. Of course “

ON

” 

means that the related LED is fixed ON and “

OFF

” means 

that the related LED is OFF.

Init Field SMS IN SMS OUT

ON

USB

1

FF

OFF

OFF

OFF

ON

OFF

2

SF

OFF

OFF

OFF

ON

OFF

3

ON

ON

OFF

OFF

OFF

OFF

4

ON

OFF

OFF

OFF

ON

OFF

5

ON

ON

ON

ON

ON

OFF

6

ON

OFF

OFF

ON

ON

OFF

7

ON

OFF

ON

ON

ON

OFF

8

ON

OFF

SF

SF

ON

OFF

9

ON

OFF

FF

FF

ON

OFF

10

OFF

SF

x

x

ON

OFF

11

OFF

SF

FF

OFF

ON

OFF

12

OFF

SF

OFF

FF

ON

OFF

13

OFF

SF

FF

FF

ON

OFF

14

FF

FF

FF

FF

ON

FF

The listed fourteen possible combinations will be here de-
scribed:

1) It identifies the 

initialization of the GSM engine

. The 

LED “

Init

” flashes quickly, with a period of  0.5 seconds

2) It   identifies   a   problem   for   the   internal   memory   of 

ModGSM

III

 module. This may mean that 

the memory 

has not been programmed or that it has been dam-
aged

. The LED “

Init

” flashes slowly with a period of 1 

second.

3) It identifies the 

switching OFF procedure

 of ModGS-

M

III

  module.   It   starts   this   procedure   when   a   power 

supply failure occurs; in this case the module does not 
switch OFF immediately, but it follows a sequence that 
has been  set  by  ModGSMTools program.  Therefore, 
for instance, it sends the SMS related to power failure 
event   and  after  the   defined   time  delay  it   completely 
switches OFF

4) It identifies a 

communication error with the GSM en-

gine

. In this case the system will force an automatic re-

boot of GSM engine after 60 seconds fixed delay

5) It   identifies  the  

critical   errors  returned   by  the   SIM 

card,   requiring   a  reboot   of   GSM  engine;   this  will   be 
automatically done after 60 seconds fixed delay

6) It identifies  

communication problems with the SIM 

card currently placed in the module. For instance, the 
SIM is not properly inserted or a SIM failure occurred. 
In this case too the system will automatically reboot the 
GSM engine after 60 seconds fixed delay

7) It identifies an 

error on entering the PIN code

, for in-

stance the entered PIN code is wrong. In this case the 
system enters a lock state waiting for the resolution of 
the error on the PIN code. This requires a proper  inter-
vention by ModGSMTools

8) It identifies an 

error on entering the PIN code

. Unlike 

the  previous  case,  this  error  will   be  reported  after  a 
normal start  of  the  GSM engine.  The  LEDs  SMS IN 
and SMS OUT flash slowly with a period of 1 second. 
In  this  case  the  system   will   automatically  reboot   the 
GSM engine after 60 seconds fixed delay

9) It identifies that the remaining 

credit of the SIM card 

expired

  and  therefore  the   SIM  has  to  be  recharged 

with a new credit. The LEDs SMS IN and SMS OUT 
flashes quickly with a period of 0.5 seconds; after 60 
seconds delay, the system will reboot the GSM engine. 
This condition will be repeated at each attempt to send 
a SMS in expired credit condition

10) It identifies the  

“normal” operation

  activity,  in other 

words the operating condition reached after the initial-
ization   and   with   no   events   pending.   The   field   LED 

  flashes with a period of 2 seconds and with an 

ON time in respect to the OFF time (duty-cycle) vari-
able   as   function   of   the   strength   of   the   GSM   signal. 
More the signal strength and more the LED will be ON 
during the period

11) It identifies the 

reception of a SMS

. The LED SMS IN 

performs a sequence of fast flashes with a period of 
0.5 seconds while the field LED continues to flash nor-
mally to shows the strength of the GSM signal

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 1.0 November 2011

Page 3 of 6

HOME AND BUILDING AUTOMATION

Summary of Contents for Contatto ModGSMIII

Page 1: ...be set to send a message at the occurrence of Contatto bus failure and or at its restoring Forwarding of SMS from ModGSMIII to user ModGSMIII can be set to forward all SMS received from not listed phone numbers to one of the listed phone numbers or to a number not inserted in the list SMS from user to ModGSMIII for command execu tion up to 64 command strings may be defined each string can execute ...

Page 2: ...I must be set by the program ModGSMTools so that to define the several parameters needed for its proper operation for more details refer to the programming manual Wiring diagram A 5 pole removable terminal block on the top side of ModGSMIII module allows the connection to the Contatto bus and to the related power supply A special connector on the top right side allow the connec tion to the antenna...

Page 3: ... gine In this case the system will force an automatic re boot of GSM engine after 60 seconds fixed delay 5 It identifies the critical errors returned by the SIM card requiring a reboot of GSM engine this will be automatically done after 60 seconds fixed delay 6 It identifies communication problems with the SIM card currently placed in the module For instance the SIM is not properly inserted or a S...

Page 4: ...described in the following only to point out some performances of the module Messages from ModGSMIII to user each SMS mes sage transmitted by ModGSMIII may report informa tion about one or more points both digital and analog ones e g temperature the composition and the con tent of the messages are fully configurable by the user through the tool program ModGSMTools This program allows to assign a w...

Page 5: ...on request For more details about the programming as said be fore refer to the specific programming manual of ModGSMIII module Technical characteristics Power supply 24V SELV 25 Current consumption MAX 0 3A 24V Internal battery 3 6V 1100mAh Li Ion Local inputs 8 Current for each input 1mA MAX MAX voltage on output contacts O1 and O2 60V 250V Contact rating O1 and O2 1A 60V 1A 250V MIN load on cont...

Page 6: ...reported on the specific data sheet of the product and according to the applicable standards All the relevant safety regulations e g accident prevention regula tions law on technical work equipment must also be observed Safety instructions Protect the unit against moisture dirt and any kind of damage dur ing transport storage and operation Do not operate the unit out side the specified technical d...

Reviews: