
55
10.4.9 High temperature protection of compressor top diagnosis and solution(P2)
Error Code
P2
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Trouble shooting:
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the unit can
start normally.
No
Check if the refrigerant
charge volume is normal?
Recharge the correct
refrigerant volume.
Refrigerant system is blocked, such
as capillary or welded point of pipes.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
No
Summary of Contents for DA1215-H1
Page 7: ...5 2 2 Part names of Indoor Outdoor units ...
Page 13: ...11 ...
Page 16: ...14 6 Wiring Diagram 6 1 Indoor Unit 12000 BTU 115 VOLT 18000 BTU 220 VOLT 24000 BTU 220 VOLT ...
Page 17: ...15 ...
Page 18: ...16 6 2 Outdoor Unit DA1215 H1 O ...
Page 19: ...17 DA1815 H2 O ...
Page 20: ...18 DA2415 H2 O ...
Page 21: ...19 For DA1215 H1 O ...
Page 22: ...20 For DA1815 H2 O For DA2415 H2 O ...
Page 23: ...21 ...
Page 54: ...52 P U P V ...
Page 55: ...53 P W P N ...