33
If the compressor stops caused by the room
temperature rising, the indoor fan will be forced
to run 127 seconds with breeze. During this
period, the anti-cold-wind is disabled.
If the machine runs in rating capacity test mode,
the indoor fan will run with rating speed and the
anti-cold-wind function is disabled.
Auto fan action in heating mode:
2.5
2
High
Low
1
Medium
1.5
9.4.3.4 Defrosting mode
Condition of defrosting:
----T4
>
0
℃
,
When the units are running, if the following two
items are satisfied, the units start defrosting:
The units run with T3
<
3
℃
for 40 minutes and
T3 keeps lower than TCDI
℃
for more than 3
minutes.
The units run with T3
<
3
℃
for 80 minutes and
T3 keeps lower than TCDI+2
℃
for more than 3
minutes.
----T4
<
0
℃
,
If the 1
st
condition and 2
nd
condition items are
satisfied, then the program judges if T2 has
decreased more than 5
℃
.When T2 has
decreased more than 5
℃
, enter the defrosting
mode.
----No matter what value T4 is, if the machine
runs with T3
<
3
℃
for more than 120 minutes
and T3 keeps lower than TCDI+4
℃
for more
than 3 minutes, the machine will enter
defrosting mode no matter if T2 drops more
than 5
℃
or not.
Condition of ending defrosting:
If any one of the following items is satisfied, the
defrosting will finish and the machine will turn to
normal heating mode.
----T3 rises to be higher than TCDE1
℃
.
----T3 keeps to be higher than TCDE2
℃
for 80
seconds.
----The machine has run for 10 minutes in
defrosting mode.
Defrosting action
:
For 9k,12k models:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
10s
no longer than 10m
30s
FrequencyF8
10s
Frequency F2
xx=60s.
For 18k,22k models:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
no longer than 10m
Frequency F8
30s
10s
10s
Frequency F2
XX=60 for 18k model, XX=90 for 22k model.
Summary of Contents for DA1215-H1
Page 7: ...5 2 2 Part names of Indoor Outdoor units ...
Page 13: ...11 ...
Page 16: ...14 6 Wiring Diagram 6 1 Indoor Unit 12000 BTU 115 VOLT 18000 BTU 220 VOLT 24000 BTU 220 VOLT ...
Page 17: ...15 ...
Page 18: ...16 6 2 Outdoor Unit DA1215 H1 O ...
Page 19: ...17 DA1815 H2 O ...
Page 20: ...18 DA2415 H2 O ...
Page 21: ...19 For DA1215 H1 O ...
Page 22: ...20 For DA1815 H2 O For DA2415 H2 O ...
Page 23: ...21 ...
Page 54: ...52 P U P V ...
Page 55: ...53 P W P N ...