6. After installation is complete, supply AC power to the emergency ballast and join the inverter connector.

7. A short-term discharge test may be conducted after the emergency ballast has been charging for one hour.

Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.

OPERATION

When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When 

power fails, the emergency ballast automatically switches to emergency power, operating one or two lamps at  

reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC 

ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown 

circuits. This emergency ballast will operate the rated lamp load for a minimum of 90 minutes.

MAINTENANCE

Although  no  routine  maintenance  is  required  to  keep  the  emergency  ballast  functional,  it  should  be  checked  

periodically to ensure that it is working. The following schedule is recommended:

1. Visually inspect the charging indicator light monthly. It should be illuminated.

2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or two

lamps should operate at reduced illumination.

3.  Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced illumination

for at least 90 minutes.

REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL

ILLUSTRATION 4

NOTE:  After installing the charging indicator light and test switch, mark each with the appropriate label.

TROFFER STYLE FIXTURE

STRIP STYLE FIXTURE

Charging

Indicator

Light

1/2" White

Bushing

Violet (+)
Brown (–)

Violet (+)
Brown (–)

1/2" White

Bushing

5/8" Black

Bushing

5/8" Black

Bushing

1/2" Punch

Fixture

Fixture

Charging

Indicator

Light

WIRING DIAGRAMS 

The following diagrams are typical schematics 

only. May be used with other ballasts. Consult 

the factory for other wiring diagrams. Emergency 

Ballast and AC Ballast must be fed from the 

SAME BRANCH CIRCUIT.

IMPORTANT TEXT: REFER TO TABLE 1 

REGARDING BROWN CONNECTOR 

Table 1 

LAMP

(DIAMETER)

BASE

TYPE

WATTAGE

(Length)

NO. of LAMPS
(EMERGENCY-

MODE)

BROWN

CONNECTOR

T8,T12

(1”, 1½”)  

Single

or

Bipin

16 - 40 W

(2'-4')

1

CLOSED

2

OPEN

40 - 215 W

(5' -8')

1

OPEN

BROWN

BROWN

BROWN CONNECTOR CLOSED

BROWN

BROWN

BROWN CONNECTOR OPEN

JUMPER 

WIRE

ILLUSTRATION 4