9

 

D)

 

Alarm Mode 

Scroll down one level and select by pressing the ENT button ALARM OFF, 
CONTINUOUS, TIMED MODE or PULSE MODE. 

1)

 

Alarm OFF 

The alarm facility connected to the PCB relay output will not be active. 

2)

 

Continuous 

The alarm facility connected to the PCB relay output will give a continuous 
alarm/siren output when the alarm is triggered. 

3)

 

Timed mode 

The alarm facility connected to the PCB relay output will give a 3 minute 
alarm/siren output when the alarm is triggered. 

4)

 

Pulse mode 

The alarm facility connected to the PCB relay output will give a 1 second pulse 
alarm/siren output when the alarm is triggered. 

 

On all the above, scroll down to MENU EXIT and press ENT to exit. 
--------------------------------------------------------------------------------------- 

 

From TEST MODE, scroll down to 

PROFILES

 and press ENT. Screen will display:- 

CUSTOMS, HI ACCESS or DOMESTIC & 100-400Kg or 400-700Kg or 700-1000Kg. 

 

1 – Customs,

 press ENT button. 

Scroll and select either, SPEED Mmin, Acc/Dec mm, LOAD=, COLL=, SBEAM and press 
ENT button. 
 
a)

 

SPEED 

 

Press ENT and start to select the following:-

 

 

OPEN=, press ENT and an arrow will appear next to OPEN=.

 

 

Select speed from Min. 8 M/min. to Max. 28 M/min with UP & Down buttons.

 

 

Press ENT button on desired speed.

 

 

Scroll down to CLOSE=, press ENT and select desired speed as above 

 

   (Close Min. speed cannot be greater than Open Min. speed) 

 

Press ENT button on desired speed.

 

 

Scroll down to CREEP=, press ENT button and an arrow will appear next to CREEP=.

 

 

Select creep speed from Min. 1.5M/min to Max. 4M/min.

 

 

 Press ENT button on desired speed.

 

 

Scroll down to CAL and press ENT button, an arrow will appear next to CAL. 

 

Select calibrating speed from Min. 5 M/min to Max. 8M/min. 

 

Press ENT button on desired speed.

 

 

Scroll down to MENU BACK and press ENT three times to exit. 

 

b)

 

Acc/Dec 

 

Press ENT and start to select the following:-

 

 

ACC= (Accelerating distance in mm) press ENT and an arrow will appear next to ACC=.

 

 

Select the distance from Min. 50MM to Max. 500mm

 

 

Press ENT button on desired distance.

 

 

Scroll down to DEC= and press ENT and an arrow will appear next to DEC=.

 

 

Select with UP or Down buttons the required distance from Min. 300MM to Max. 990mm.

 

 

Press ENT button on desired distance.

 

 

Scroll down to NORM CLOSE or POS CLOSE (Presently not in use), press ENT to select 

the required CLOSE.

 (Select at present only NORM CLOSE)

 

a)

 

Norm Close, Gate must not bump in close or open position. (+- 15 – 20 mm Gap)

 

 

Summary of Contents for 600 Elite

Page 1: ...nstructions E EEEE DTS SLIDING GATE MOTOR INSTALLATION MANUAL DTS 600 Elite with SL150 PCB DTS SECURITY P O BOX 3399 EDENVALE 1610 TELEPHONE 086 1000 387 Spartan 2711 392 5540 H O Pretoria 2712 361 5528 www dtssecurity co za ...

Page 2: ...ory defaults Default setting Code Error message Auto close 10 sec 90 Mains OFF Battery voltage below 10 5V Pedestrian 1 meter 5 sec 91 Motor timed out Auxiliary Relay Gate light 92 No error for this number Alarm mode OFF 93 Limit switch error Check open close limits 100 400Kg Speed Open 25M min 94 Collision detected collision setting to low Close 25M min 95 Motor stall with low current Check load ...

Page 3: ... plate with bolts 160mm from the centre of the gate track and centre of base plate a minimum of 250mm away from the gate opening 3 Secure the base plate to the gate track by welding the base plate directly to the gate track Ensuring a distance of 160mm from centre of gate track to centre of fastening screws 4 Fit all required cabling through hole provided in base plate 5 Support the back of the ba...

Page 4: ...Ensure that one of the screws attaching the nylon rack to the angle is in line with the read switch or limit switch spring when the gate is fully closed and open position Limit switch actuator mounting instructions 1 Remove the screw attaching the nylon rack to the angle that is closest to the position of the reed switch or the spring on the motor when the gate is in the close and open position 2 ...

Page 5: ...SU AND LOW VOLTAGE TRANSFORMER 16V AC TOGETHER IF 220V IS USED AT GATE MOTOR A SEPARATE DOUBLE POLE ISOLATOR MUST BE FITTED WITHIN 1Meter FROM MOTOR COURTESY LIGHT OUTPUT Will stay on for 3 minutes after a trigger is received Please note that the Amps usage on the courtesy lights must not exceed 10Amps If this facility is not being used it can then be utilized as a tamper alarm facility see page 1...

Page 6: ... beams are connected CL and TX CMN on the PCB by the Safety beams MUST be bridged Also NOTE IR beams must be fitted if a DTS600 motor is installed Diagrams for gate open triggers NB When connecting intercoms to the control card TRG or PED please ensure that your intercom trigger output is potential free ZERO voltage If not a gate relay module must be fitted ...

Page 7: ...one from a black screen pressing the ENT button twice the Screen will display the following TEST MODE SETTINGS PROFILES REMOTES RUN STATUS and GEN STATUS In TEST MODE press ENT button Screen will display the following TRIG GATE and AUTOSET 1 Trig Gate Press ENT button to trigger Gate to open or close Press ENT button to exit 2 AUTOSET Press ENT button to start calibration of gate motor Press ENT b...

Page 8: ...me in seconds required Min 1 second to Max 179 seconds Press ENT button on desired seconds Scroll down to Mtr Press ENT button and an arrow will appear next to Mtr By using the Up or Down arrow buttons select the opening distance required Press ENT button on desired distance Scroll down to MENU BACK and press ENT twice to exit 6 Auxiliary Relay Default Gate light From TEST MODE scroll down to SETT...

Page 9: ...t speed from Min 8 M min to Max 28 M min with UP Down buttons Press ENT button on desired speed Scroll down to CLOSE press ENT and select desired speed as above Close Min speed cannot be greater than Open Min speed Press ENT button on desired speed Scroll down to CREEP press ENT button and an arrow will appear next to CREEP Select creep speed from Min 1 5M min to Max 4M min Press ENT button on des...

Page 10: ...C CONDO Auto close will be ON If Domestic is selected then PIRAC CONDO Auto close will be OFF On both of the above PIRAC CONDO Auto close can still be change as required 3 100 400Kg or 400 700Kg or 700 1000Kg Force requirement Generally select 400 700KG Select the required Kg gate weight by pressing the ENT button Press ENT button to exit From TEST MODE scroll down to REMOTES and press ENT Screen ...

Page 11: ...er location will appear next to LOC EG LOC 4 Press the ENT button and that remote will show as delete If the transmitter is not available but the number is known Scroll down to LOC and press ENT button An arrow will appear next to LOC Use the UP or Down buttons to select the required transmitter button Press the ENT button and scroll up to DELETE Press the ENT button and that transmitter number wi...

Page 12: ... gate reaches its open limit then press hold the transmitter or manual push button for approximately 4 sec The control card will give 1 long beep to confirm the override To reactivate the auto close press and release the transmitter or manual push button 4 Condominium free exit loop When condominium free exit loop is activated on the unit the unit will not respond to any transmitter or manual push...

Page 13: ...he gearbox release and pressing the remote control push button confirmed by 3 short beeps The alarm will remain disabled until the gearbox release is closed and the gate closed position re confirmed 8 Anti hijack Alarm a When the tamper alarm function is active and the gate receives a valid trigger but is obstructed and cannot move or did not move more than 150mm the alarm or siren will activate b...

Page 14: ...0ms beeps Check motor load fuse 25amp Check motor brushes and armature PCB reader not picking up Magnet on motor Five 1 second beeps Holiday lockout mode has been de activated Twenty 100ms beeps Motor has stalled or overloaded then check the following points 1 Gate pulling force should not exceed 15kg 2 Load pot is set too low Turn pot completely clockwise 3 Battery voltage under load Should not d...

Page 15: ...he Safety beams MUST be bridged Note 1 The 12V OUT on the 600 PCB is a regulated voltage up to 12Volt DC 2 Please ensure that the auxiliaries connected to the 12 volt auxiliary output do not exceed 500 m Amps in total If so remove from aux output and connect directly to battery ...

Page 16: ...Volt Motor is in holiday lockout DO NOT do a Factory Default Motor Load fuse is faulty or motor brushes not making contact with armature 12 Volt aux output of 500m Amps have been exceeded Replace transmitter battery Check with supplier Follow the receiver setup instructions Check wiring between PCB and push button Replace the reed switch and or the magnet For short term solution bridge out the two...

Page 17: ...rd Encoder is faulty Clear obstruction or adjust load sensing Clear obstruction Check with other operators on the system Turn ring magnet on the motor by hand if no activity on the encoder LED contact supplier Check that the PCB is fitted correctly Gate does not remain open Auto close has been activated Another user has triggered the unit Condominium loop and or Pirac mode has been activated Dipsw...

Page 18: ...nge limit switch or check with supplier Gate motor is jumping teeth on the rack Pinion to rack spacing is incorrect Rack is insufficiently fastened to gate leaf Debris on track Re align Re align and correct fastening Clean track Gate jams in the open or closed position and is not easy to manually release Gate opens pedestrian when full open trigger is given PCB does not beep 1 5 beeps on closing t...

Page 19: ...arranty excludes lightening damage insect damage and damage caused by faulty installation In the event of the goods being supplied by dealer merchant agent or duly appointed installer of DTS Security Products the claim must be directed to that supplier The carriage of goods is for the customer s account This warranty is only valid if the correct installation and application of goods as laid out in...

Reviews: