3-2 INPUT CONNECTIONS
1.
Verify that power source to the unit is OFF, locked and tagged according to
OSHA requirements.
CAUTION
Verify that the input voltage as stated on the UPS nameplate, matches the
customer-supplied voltage. If the voltage does not match, STOP installation of the
UPS and contact Customer Service at DSPM.
2.
Verify that Input cable and conduit are routed correctly and are in position to
connect the unit.
3.
Open front doors of UPS
4.
Select desired mounting location and connect conduit.
5.
Pass wires through the mounting hole.
6.
Secure conduit fitting to the panel of unit.
7.
Connect input wires to the input, neutral and ground terminal blocks. These are
pre-wired to the input circuit breaker.
(Input terminals blocks and Main breaker)
(TB1) L1 /L2 /L3 / N /G