SECTION 4 - OPERATIONS
4-1 STARTING THE UPS
1. Check the input A.C. Circuit Breaker is OFF.
2. Check all output Circuit Breaker(s) (optional) are OFF.
3. Check the Battery Circuit Breaker(s) are OFF.
4. Energize the Utility feeder to the unit.
5. Turn Input Circuit Breaker ON.
6. Wait for the System display message instructing you to close the battery breaker.
7. Turn on the Battery Circuit Breaker.
8. Wait for the System Display message stating that the unit is operational.
9. Turn on the Output Circuit Breaker(s).
System Display Panel