Description of Controls
Page 37 of 74
057-276 ISSUE: 1.3
4.2.3 WHEN CONNECTED TO DSE8610 MKII
Icon
Description
Auto Mode
This button places the module into its
Auto Mode
.
This mode allows the
module to control the function of the generator automatically. The module
monitors various remote start
functions and once a start request is made, the set
is automatically started, synchronises and placed on load
(‘Close Generator’
become active)
.
Upon removal of the starting signal, the module removes the load from the
generator and shut the set down observing the
stop delay
timer and
cooling
timer
as necessary
(‘Close Generator’ becomes inactive)
. The module then waits for
next start event.
Manual Mode
This button places the module into its
Manual Mode
. Once in
Manual Mode
, the module responds to the
Start
button to start the
generator and run it off load.
To place the generator on load, use the
Close Generator
button. The
module automatically instructs the generator to synchronise if required and then
closes the generator load switch
(‘Close Generator’ becomes active)
.
To place the generator off load, use the
Open Generator
. The module
automatically instructs the generator to ramp down if possible and open the
breaker
(‘Close Generator’ becomes inactive)
.
If the engine is running off-load in
Manual Mode
.and an on load becomes
active, the module automatically instructs the changeover device to place the
generator on load instructs the generator to synchronise if required and then
closes the generator load switch
(‘Close Generator’ becomes active)
.
Upon removal of the on load signal, the generator remains on load until either
selection of the
Stop/Reset Mode
or
Auto Mode
.
Alarm Mute / Lamp Test
This button de-activates the audible alarm on the module, the
Audible Alarm
output (if configured) and illuminates all of the LEDs on the module’s facia.