Setup Procedure
057-295 ISSUE: 1
Page 36 of 60
4.4.2 ALTERNATE STABILITIES
NOTE: Ensure the setup procedure had been carried out according to the Stability
Configuration selected.
The AVR is provided with two
Alternator Stability
configurations (DIP Switch 1).
Function
DIP Switch 1
Stability Configuration 1
OFF
Stability Configuration 2
ON
4.4.3 ALTERNATE CONFIGURATIONS
DIP switches are used to select between different configurations within the device. Each configuration
is adjusted using DSE Configuration Suite PC Software to
suit the application’s nominal Voltage and
Frequency.
DIP Switches 2, 3 & 4 selects one of six Configurations.
With the generator set stopped, observe the settings on the SCADA
Diagnostic
display and set the
dip switches to the desired positions.
Function
DIP Switch 2
DIP Switch 3
DIP Switch 4
Main Configuration
OFF
OFF
OFF
Alternative Configuration 1
OFF
OFF
ON
Alternative Configuration 2
OFF
ON
OFF
Alternative Configuration 3
OFF
ON
ON
Alternative Configuration 4
ON
OFF
OFF
Alternative Configuration 5
ON
OFF
ON
4.4.4 PROTECTIONS
Verify the setting on the
Protections
menu.
Change
Start-up Fail Delay
to the
desired time (this was changed earlier
in the setup procedure to ease the
setup process), the factory default 3.0
seconds is suitable for most generator
sets.
Use the SCADA section of the
Configuration Suite PC Software to
check the
Excitation Voltage
during
normal operation, at a high load level.
Set the
Over Excite Trip
slightly above
this level.