Setup Procedure
Page 21 of 60
057-295 ISSUE: 1
Using DSE Configuration Suite PC Software,
select the appropriate
Voltage Set Point
.
The
Low Voltage Range
(for 90 V to 300 V
systems) or
High Voltage Range
(for 180 V to
600 V systems).
This voltage refers to the voltage applied to the
AVR
’s L1, L2 (N) & L3
terminals (the sensing
voltage).
Select the appropriate
AC Sensing
topology
being used
for the AVR’s L1, L2 (N) & L3
terminals
Now select the
Set Point
menu and ‘uncheck’
the
Preset Enable
option.
This allows the
Set Point
parameter to be
configured to a specific value.
Leave the
Droop
and
External Bias
settings in their default states initially, these are to be addressed
later.
Using DSE Configuration Suite PC
Software, select the appropriate
Frequency Range
(50 Hz or 60 Hz).
Uncheck the
Preset Enable
option.
This allows
Under Frequency Roll
Off Knee Point
to be adjusted if
required.
To ease setup, adjust
Knee Point
to
a low value to prevent
Under
Frequency Roll Off
from activating
during the setup procedure.
Set the
Under Frequency Trip Point
as required.
‘Uncheck’
Preset
Enable
....
and configure the
Set Point
.
‘Uncheck’
Preset
Enable
....
and
configure
the
Knee
Point