Setup Procedure
057-295 ISSUE: 1
Page 34 of 60
4.4 FINALISING SETUP
NOTE: For further details of module configuration, refer to DSE Publication: 057-271
DSEA109 Configuration Suite PC Software Manual.
4.4.1 PRESETS
WARNING!: Use only a suitable insulated potentiometer (preset) adjustment tool.
Presets are the adjusters fitted on the AVR and may be disabled if end user adjustment is not
required.
When enabled, the range of the presets is configurable using the DSE Configuration Suite PC
Software to enable the generator assembler to limit user adjustment within a range suitable for the
completed generator.
Location of Presets
Voltage Set Point
Droop
U.F.R.O.
Proportional
Integral