4.2.3 DSE9155
Connector A
Terminal
Function
Recommended size
Comments
-OP
Load negative
1mm² (AWG 16)
Battery negative terminal
+OP
Load Positive
1mm² (AWG 16)
Battery positive terminal
BOOST
N/A
0.5 mm² (AWG 22)
Boost not avaialble on DSE9155
BOOST
N/A
0.5 mm² (AWG 22)
CF
Charge failure relay
0.5 mm² (AWG 22)
Closes under charge fail conditions
CF
Charge failure relay
0.5 mm² (AWG 22)
Connector B
Terminal
Function
Recommended Size
Earth
1mm² (AWG 16)
N
AC Neutral
1mm² (AWG 16)
L
AC Live
1mm² (AWG 16)
CAUTION: Ensure Earth Terminal is connected to Battery negative (for negative earth
systems) or Battery positive (for positive earth systems).
Where no system earth exists, Earth Terminal must be connected to battery negative.