DSE Model 5210 Automatic Start Engine Management and Instrumentation System Operators Manual
8
057-011 5210 OPERATING MANUAL ISSUE 5.1 18/06/2007 AM
3.2 MANUAL
OPERATION
NOTE:- If a digital input configured to panel lock is active, the LCD will display the
icon. When in panel lock, changing module modes will not be possible. Viewing the instruments
and event logs
is NOT affected by panel lock.
To initiate a start sequence in
MANUAL
, press the
pushbutton. When the controller is in the manual mode
(indicated by an LED indicator beside the button), pressing the
START
(I) button will initiate the start sequence.
NOTE:- There is no Start Delay in this mode of operation.
If the
pre-heat
output option is selected this timer is then initiated, and the auxiliary output selected is energised.
The
Fuel Solenoid
is energised, and then the
Starter Motor
is engaged.
The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the
starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of
attempts, the start sequence will be terminated and
Fail to Start
fault will be displayed accompanied by a flashing shutdown
indicator.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator
output. Alternatively, a Magnetic Pickup mounted on the flywheel housing can be used for speed detection (This is
selected by PC using the 5200 series configuration software). Rising oil pressure can also be used to disconnect
the starter motor; however, it cannot be used for underspeed or overspeed detection.
After the starter motor has disengaged, the
Safety On
timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.
Once the engine is running, the
Warm Up
timer, if selected is initiated, allowing the engine to stabilise before it can
be loaded.
The generator will run off load, unless a
Remote Start
signal is applied, and if
Load Transfer
has been selected
as a control source, the appropriate auxiliary output selected will activate.
If the
Remote Start
signal is removed, the generator will continue to run
On
load until the
Auto
mode is selected.
The
Remote Stop Delay Timer
will time out, the load is then disconnected. The generator will then run
off
load
allowing the engine a
cooling
down period.
Selecting
STOP (O)
de-energises the
FUEL SOLENOID
, bringing the generator to a stop.