Options 3, 4 - Zone Fault, Zone Fault Restores

Modes 2, 3

When the system sees a short circuit across any zone, a zone fault is generated.
DEOL resistors are required for zone fault reporting. In Section [11], Option [2] 
must be set to OFF and Option [3] must be set to ON; In Section [13], Option 3 
must be set to ON and the Skyroute CL3050 must be operating in mode 2 or 3.
Option 3. 

Default -

 OFF

Option 4. 

Default -

 OFF

Options 5, 6 - Zone Tamper, Zone Tamper Restores

Modes 2, 3

When the system sees an open circuit across any zone a zone tamper is gener-
ated. DEOL resistors are required for zone tamper reporting. In Section [11], 
Option [2] must be set to OFF and Option [3] must be set to ON. In Section [13], 
Option [3] must be set to ON and the Skyroute CL3050 must be operating in 
mode 2 or 3.
Option 5. 

Default -

 OFF,

 

Option 6. 

Default -

 OFF

Option 7 - System Maintenance Events

All Modes

When this option is enabled, the maintenance events enabled in Section [21] are 
transmitted using the codes listed in appendix A.

Default -

 ON,

Option 8 - Generic Zones

Modes 2, 3

The Skyroute CL3050 supports generic and detailed zone alarm reporting.  By 
default, the Skyroute CL3050 will be in generic zone reporting mode.  When in 
this mode, all zone types are divided into four reporting groups; BA Burg, FA Fire, 
PA Panic, UA Technical.  If any zone from this group initiates a transmission, the 
generic reporting code for this event is sent, additional violations from other 
zones from the same group will be ignored until that group's timer has expired. 
See table below for zone type grouping.

Zone

Type

Detailed 

Reporting Code

Generic 

Reporting Code

Null

Burglary

Fire

Panic

Technical

Gas

Heat

Medical

Emergency

Water

Freezer

Sprinkler

Hold-up

-

BA

FA
PA

UA

GA

KA

MA

QA

WA

ZA
SA

HA

-

BA

FA
PA

UA
UA

FA
PA
PA

UA
UA
UA

PA

Each zone group has it's own timer.  The default time is 5 minutes and is pro-
grammed in Section [23].  If any zone in a group initiates an event, the timer will 
start running and the generic event will be sent.  If any additional zones from the 
same group initiate an event before that group's timer expires, the event will be 
ignored.  This generic zone reporting mode only applies to zone alarms.  Alarm 
restorals, tamper/tamper restorals and fault/fault restorals are not grouped 
together into generic reporting groups.

Summary of Contents for Skyroute CL3050

Page 1: ...PowerSeries keypads Installation Programming Guide WARNING This manual contains information on limitations regarding product use and function and information on the limi tations as to liability of the...

Page 2: ...ocation may be required STEP 2 CONNECT NECESSARY WIRING See Section 6 Mount the Skyroute determine the desired mode of oper ation and connect the appropriate control panel zone or Keybus wiring as det...

Page 3: ...found on the authorized Installer Card sent with the Dealer Confirmation Form Installer PIN Number 4 digits I___I___I___I___I Each Installer provided a 4 digit PIN number on the Dealer Enrollment Form...

Page 4: ...riel brouilleur du Canada IC 160A CL3050 The term IC before the radio certification number only signifies that Industry Canada technical specifications were met Limited Warranty DSC warrants that for...

Page 5: ...gramming Descriptions 9 01 Zone 1 2 Definitions 9 02 Zone 3 8 Definitions 9 03 Zone 1 2 Loop Response 9 10 Skyroute CL3050 Mode of Operation 9 11 Skyroute CL3050 Configuration Options 1 10 12 Skyroute...

Page 6: ...ii...

Page 7: ...of the con trol panel The system identifies the Bell Output cadence and transmits the corre sponding Fire or Burglar alarm reporting code to Connect 24 Refer to the appropriate control panel Installat...

Page 8: ...erSeries Keypads PC5508 KP5508Z 8 Zone LED keypad PC5516Z KP5516Z 16 Zone LED keypad PC5532Z KP5532Z 32 Zone LED keypad LCD5500Z KPL5500Z Programmable Message LCD Keypad LCD5501Z KP5501Z Fixed Message...

Page 9: ...ming Descriptions section 10 for zone wir ing details Note Generally the higher the location and the closer that the Skyroute CL3050 is to an outside wall the better the signal strength will be 3 Chec...

Page 10: ...s will send a test transmission to the central station via Connect 24 Refer to Enrol Button in Section 3 Controls and indicators for test transmission details Mode 1 Disable the telephone line connect...

Page 11: ...h a series of flashes as indicated below No of Flashes Indication 1 2 3 4 5 6 7 8 9 No trouble conditions present Low battery Input supply failure Not enrolled at Connect 24 No service available Radio...

Page 12: ...ce will display the detailed RSSI status indicated above Holding this button down for a period of 2 seconds continuously will cause the Skyroute CL3050 to send a test transmission to Connect 24 this l...

Page 13: ...found it will automatically configure itself for mode 3 If no Keybus modules are present the Skyroute CL3050 will power up in mode 1 During the first 15 seconds of power up any zone scanning will be s...

Page 14: ...ered down 1 Connect keypad Keybus connections to the RED BLK YEL and GRN termi nals of the Skyroute CL3050 2 Connect a 12VDC supply across the RED and BLK terminals Upon detecting the keypad on power...

Page 15: ...ffect zones on a PC5108 zone expander card Default 05 0 5 seconds 01 FF Hex x 0 1 seconds 10 Skyroute CL3050 Mode of Operation 01 Mode 1 Bell Follower Operation In this mode the YEL terminal is con ne...

Page 16: ...that occur to the central station Note This configuration can not be used with an AC supply Note Jumpers on the PC5108 must be set as follows J1 J2 J3 ON OFF ON J4 J5 J6 OFF OFF ON Default 01 03 depen...

Page 17: ...r the Skyroute CL3050 to resume communications Default Not Enrolled Options 7 8 System Use All Modes Caution Do NOT change these settings unless it is requested by DSC technical support personnel Defa...

Page 18: ...rvice Available All Modes This trouble is indicated If the system is unable to detect cellular service Default ON Option 5 Radio Failure All Modes This trouble is indicated if there is an internal fau...

Page 19: ...fic volume when selecting test transmission times select a time that is not on the 30 minute mark e g 02 24 04 07 18 Test Transmission Day All Modes When the Skyroute CL3050 is powered up for the firs...

Page 20: ...Zones Modes 2 3 The Skyroute CL3050 supports generic and detailed zone alarm reporting By default the Skyroute CL3050 will be in generic zone reporting mode When in this mode all zone types are divide...

Page 21: ...system will send a restore Default ON Option 3 Skyroute CL3050 Tamper All Modes Removing the cover on the Skyroute CL3050 will send a tamper reporting code to Connect 24 Default OFF Option 4 PC5108 Mo...

Page 22: ...lt 05 I___I___I Zone 1 05 I___I___I Zone 2 10 Skyroute CL3050 Mode of Operation Default 01 I___I___I 01 Bell Follower 02 2 Zone 03 8 zone PC5108 11 Skyroute CL3050 Configuration Options 1 Default Opt...

Page 23: ...59 Hrs Mins 16 System Day Default Opt Option On Option Off ON I___I 1 Sunday Disabled OFF I___I 2 Monday Disabled OFF I___I 3 Tuesday Disabled OFF I___I 4 Wednesday Disabled OFF I___I 5 Thursday Disab...

Page 24: ...es Disabled ON I___I 7 System Maintenance Events Disabled ON I___I 8 Generic Zone Reporting Detailed Zone Reporting 21 System Event Communication Options Default Opt Option On Option Off ON I___I 1 In...

Page 25: ...ndication This value is transmitted to Connect 24 during the periodic test transmission and can be viewed after power up by pressing the enroll button SID System Identification Number ID Number of the...

Page 26: ...AXX E154 Water Zone WHXX R154 Freezer Zone ZAXX E140 Freezer Zone ZHXX R140 Sprinkler Zone SAXX E110 Sprinkler Zone SHXX R110 Hold up Zone HAXX E122 Hold up Zone HHXX R122 Zone Fault Alarms Zone Fault...

Page 27: ...X E137 Water Zone TRXX R137 Freezer Zone TAXX E137 Freezer Zone TRXX R137 Sprinkler Zone STXX E200 Sprinkler Zone SJXX R200 Hold up Zone TAXX E137 Hold up Zone TRXX R137 Generic Zone Events System Eve...

Page 28: ...2002 Digital Security Controls Ltd Toronto Canada 1 800 387 3630 www dsc com Printed in Canada 29034531r001 Forward comments about this manual to pubs dsc com...

Reviews: