background image

3

2.3 Wiring

1. Before beginning to wire the unit, ensure that all power (AC transformer and bat-

tery) is disconnected from the control panel.

2. Connect the four Keybus wires from the con-

trol panel (red, black, yellow and green) to
the keypad terminals (R B Y G). See the dia-
gram at right:

3. You can connect two devices - such as door

contacts - to the Z1 and Z2 terminals of the
PC5502Z2. To connect the zone, run one
wire from the device to the Z terminal and
the other wire from the device to the B
(black) terminal. For powered devices, run the
red wire to the R (positive) terminal and the
black wire to the B (negative) terminal. 
When using end of line supervision, connect
the zone according to one of the configura-
tions outlined in your system’s 

Installation

Manual

.

NOTE:

 The PC5502Z2 zones will follow the end-of-line supervision option

selected for the main panel. Please refer to your panel’s Installation Manual for
more information.

2.4 Applying Power

Once you have completed all the wiring, apply power to the control panel: 
1. Connect the battery leads to the battery

2. Connect the AC transformer. 

For more information on control panel power specifications, see the control panel 

Instal-

lation Manual

.

NOTE: 

Do not connect the power until all wiring is complete.

2.5 Testing the System and PC5502Z2 Keypads

You cannot perform a system test from the PC5502Z2 keypad. To conduct a system test
at the system keypad, please refer to your system’s 

Installation Manual

 and 

Instruction

Manual

.

Now that you have connected the PC5502Z2, you will need to enroll it with the control
panel. Please see section 3 for instructions.

Summary of Contents for PC5502Z2

Page 1: ...n on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5502Z2 Installation Manual 1999 Digital Security Controls Ltd 1645 Flint Road Downsview Ontario Ca...

Page 2: ...need to be replaced this monitor may fail to operate as expected Regular testing and maintenance will keep the system in good operating condition Compromise of Radio Frequency Wireless Devices Signals...

Page 3: ...e PC5502Z2 to a Keypad Zone on page 14 Program the keypad zone assignment in the main panel Installer s programming at the system keypad Refer to your system s Installation Manual for instructions Key...

Page 4: ...oses other than those for which it was designed damage from improper maintenance damage arising out of any other abuse mishandling or improper application of the products Digital Security Controls Ltd...

Page 5: ...ad PC5508Z PC5516Z PC5532Z or LCD5500Z to use for programming the main control panel and for monitoring the status of the entire system Mount the system keypad in an area accessible only by personnel...

Page 6: ...labels 2 2 Mounting You should mount the keypad where it is accessible to designated points of entry and exit Once you have selected a dry and secure location perform the following steps to mount the...

Page 7: ...tions outlined in your system s Installation Manual NOTE The PC5502Z2 zones will follow the end of line supervision option selected for the main panel Please refer to your panel s Installation Manual...

Page 8: ...ssigned to slot 11 by default You must assign each keypad to its own slot 11 to 18 for it to be properly supervised by the system NOTE PC5502Z2 keypads should only be enrolled on partition 1 To enroll...

Page 9: ...D5500Z or DLS software You cannot enter the programming sections for the main panel from PC5502Z2 keypads 4 1 How to Program the PC5502Z2 This section describes how to program a PC5502Z2 It is a good...

Page 10: ...s pro gramming NOTE After you exit from Installer s programming all bypassed zones will be cleared unbypassed 4 2 Setting up PC5502Z2 Zones and Zone Options Each PC5502Z2 keypad can supervise two zon...

Page 11: ...med the PC5502Z2 will wait the programmed amount of time and then pass the alarm on to the main panel The main panel will then immediately communicate the alarm to the central station The bell will so...

Page 12: ...tion is on interior by default When this option is turned on zones programmed as type 04 will work as described in the Stay Away zone description page 6 When this option is turned off delay zones prog...

Page 13: ...ds for the exit time The keypad sounds 4 quick beeps 5 If you want you can now program another section To exit programming press 4 5 Programming Quick Arm and Quick Exit Options You can program the fo...

Page 14: ...tay Arm 01 Away Arm 02 Chime 04 Sensor Reset 09 and Quick Exit 10 To use a function press and hold the appropriate key for two seconds Users may also need to enter an access code after pressing the fu...

Page 15: ...Programming by pressing 8 Installer s Code 2 Enter one of the following sections to turn on the access code requirement for a par ticular function key 45 for Function Key 1 46 for Function Key 2 47 fo...

Page 16: ...ram the amount of time the alarm will sound locally in 50 Local Alarm Duration Timer Program an amount of time from 001 to 255 seconds If you program 000 seconds the PC5502Z2 will not sound a local al...

Page 17: ...n now enter another programming section or to exit program ming press 32 Keypad Blanking This option is off by default If the Keypad Blanking option is turned on the PC5502Z2 will turn off all keypad...

Page 18: ...olled all installed PC5502Z2 keypads into indi vidual slots See Enrolling the PC5502Z2 on page 4 To assign the PC5502Z2 to a keypad zone 1 At the system keypad not the PC5502Z2 keypad enter Installer...

Page 19: ...or each system zone For each PC5502Z2 zone enter a 2 digit zone definition We recom mend that you program each PC5502Z2 keypad zone as a 24 Hour Burglary zone 11 This will ensure that alarm informatio...

Page 20: ...ling the PC5502Z2 on page 4 Valid entries are 11 18 i e enter 11 for slot 1 12 for slot 2 etc Default 11 NOTE PC5502Z2 keypads should only be enrolled on partition 1 Slot I_______I_______I 01 05 Funct...

Page 21: ...4 Programming Entry and Exit Times on page 9 Valid entries 001 255 seconds Entry Time Exit Time Default 030 Default 120 I_______I_______I_______I I_______I_______I_______I 25 Master Code 4 7 Programmi...

Page 22: ...I_______I OFF 4 6 10 48 Function Key 4 Requires Code I_______I OFF 4 6 10 49 Function Key 5 Requires Code I_______I OFF 4 6 10 50 Local Alarm Duration Timer 4 8 Setting Up the PC5502Z2 to Sound Alarm...

Page 23: ...need to be replaced this monitor may fail to operate as expected Regular testing and maintenance will keep the system in good operating condition Compromise of Radio Frequency Wireless Devices Signals...

Page 24: ...n on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5502Z2 Installation Manual 1999 Digital Security Controls Ltd 1645 Flint Road Downsview Ontario Ca...

Reviews: