Programming Section Descriptions
If you will be connecting the PC5400 to a PC5010, PC5015, PC1555 or PC580 control panel, access the
PC5400 programming sections at a system keypad by entering [*][8][Installer's Code][803]. Then enter
the 2-digit number of the section you want to program.
If you will be connecting the PC5400 to a PC1575, access the PC5400 programming sections at a
system keypad by entering [*][8][Installer's Code][87]. Then enter the 2-digit number of the section you
want to program.
Section [06], Option [2]: AC Communications
To change from standard DVACS (150 baud) to AC communications protocol (300 baud) program this
option as ON.
Section [07]: Subsystem Number
Program the DVACS Subsystem number in this section.
Section [08]: Group Number
Program the DVACS Group number in this section.
Section [09]: Panel DVACS Identifier Code
Program the DVACS ID code in this section.
Sections [10-17], and [50-52]: DVACS Reporting Codes
Program the DVACS reporting codes in these sections (see Appendix A: ADT DVACS Transmission
Table):
• To have the PC5400 transmit a pre-programmed code from the internal table, leave the
programming at the default value FF.
• To prevent the PC5400 from reporting an event, program the code as 00.
• To have the PC5400 transmit a different code, program a value from 01-FE.
Sections [18-27]: Transmission Options
To prevent the PC5400 from transmitting a group of reporting codes (e.g. zone troubles or zone trouble
restorals) program the appropriate option as OFF. All options are ON by default.
Sections [28-35]: Zone Assignments
The programming in these sections tells the PC5400 which partitions each zone is assigned to (on
control panels which are capable of partitioning) and/or which zones in active use.
If the PC5400 is connected to a control panel using partitions, make sure that the zone/partition
assignments match those programmed in the control panel.
If the PC5400 is connected to a control panel without partitions, you must still program these sections:
for each used zone on the control panel, turn ON the option that assigns the zone to partition 1.
Sections [36-39]: Zone Definitions
Make sure that the zone definitions match those programmed in the control panel.
NOTE: If you change any of the above options from the default settings, test the PC5400 to make sure
it is operating as desired.