background image

5

Battery Troubles

If a zone has a low battery trouble, then that zone does
not report in with a zone supervisory within the
"supervision time". The zone will not go into alarm. This
has been included to reduce the possibility of a false
alarm from batteries that do not get changed in the
zone, and then the zone going into sensor fault.

Restoring Battery Troubles

A wireless zone battery trouble will only be restored
after that zone has been Tampered and Restored. This
will allow the batteries to be changed without multiple
Battery trouble/Battery restoral transmissions taking
place. In order for the batteries to be changed the cover
must be removed from the back plate (tampering the
zone). When the tamper is restored and the zone sends
a battery trouble restoral (as well as the tamper restoral)
signal to the PC4164, the battery trouble will clear.

Default Srl #'s (4)

Once this selected has been made the LCD will display
the message "Confirm Default Press 

". To abort press

any other key. Once the [

] key has been pressed the

LCD will display the message "Resetting ". All RF zone
signatures will have been erased from the PC4164.

Note: Deleting the RF signatures from the PC4164
will not remove the zone(s) from the partition
assignment(s).

COMBUS Power and Operation

The PC4020 main board can provide up to 500 mA to
power modules, keypads and devices. A PC4204 power
module is required when additional current is needed
either for powering detection devices or operating bells
and sirens. The PC4204 requires its own transformer
and battery and can provide up to 1.5A at 12 V

DC

. Four

relays on the module provide form C switched outputs
with contact ratings of 3 amps @ 12 V

DC

 (10 amps @ 120

VAC) for a variety of programmable options. When used
to repower the COMBUS the PC4204 must be wired in
accordance with the instructions supplied with the unit.
Use of a power source other than the PC4204 power
supply module to supply additional power to the PC4020
system is not recommended for the following reasons:

If the main panel loses communications with a module,
within a maximum of 30 seconds the panel will perform a
system reset in which power to the COMBUS is
removed. Five seconds later power is reapplied and the
panel will attempt to communicate with the module. If
the panel is unsuccessful communicating with the
module it will display and report a COMBUS
communications fault.

When the main panel performs a reset, relay 1 when
programmed for “COMBUS POWER” will open. This will
disconnect the power supplied to the modules, resetting
them so that communications to the main panel are
reinitialized.

For example, if the microprocessor on the module has
been scrambled due to a transient, the PC4020 will

power down the COMBUS, the PC4204 will mimic the
PC4020 and cut off its power supply to the module. The
module will be powered down. When the PC4020 returns
power to the COMBUS, the PC4204 will reconnect its power
supply, and the power to the module will return. Because
the module was powered down and powered up, the
module is now reset, and can communicate with the
PC4020.

If a power supply other than a PC4204 was used, the
module would never power down, never reset, and the
module will stay off line requiring the attention of service
personnel.

CAUTION: When used to power a module, the “RLY 1
COM” terminal of the PC4204 must be connected to the
“RED COMBUS” terminal of the module only. The
positive (RED) conductor of the COMBUS must be left
unconnected to the module that is powered by the
PC4204. The “BLK COMBUS” of the module should be
run common to the negative (“BLK”) of the COMBUS.
Use of a power source other than the PC4204 power
supply module to supply additional power to the PC4020
system is not recommended.

The COMBUS is a four conductor cable to which all
modules and keypads are connected in parallel.
Connections to the COMBUS do not have to be home-run.
For example if a storage building had an 8 zone expander
(PC4108) and a keypad (LCD4500 ) located in it, the zone
expander and keypad could be spliced together and run
back on a single 4 wire cable to the nearest point on the
COMBUS.

KEYPAD

R
B
Y
G

R
B
Y
G

R B Y G

COMBUS

PC4020

PC4108

Testing The Combus

To test the Combus for a low voltage condition, connect all
devices to the system (include any motion dectectors, glass
break detectors, etc.) and enroll each of the modules. Exit
installers mode and allow the system to run normally for 5 -
10 minutes. This will allow time for any modules that may
have battery troubles time to report. If after this time there
are any battery troubles be sure that the batteries are
"good" by disconnecting the suspect battery and placing a
voltage meter accross the battery leads (of the module); the
output voltage should be 13.85V. If the voltage is good then
check the battery (under load), even if the battery is under
a load the voltage should still be above 12.0V. Once all (if
any) battery troubles have been taken care of, be sure that
there are no Combus Low Voltage troubles. If there are
locate the modules with the low voltage troubles by entering
Installers Mode and selecting Diagnostics. Refer to
Appendix B for the List of Diagnostics. Once the module(s)
have been isolated a PC4204 will be required to increase
the power to be module with the low voltage trouble. Now
that all trouble have been taken care of the next step is to
remove AC power from all modules and allow the panel to

Summary of Contents for maxsys PC4020KT

Page 1: ...k 1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read ...

Page 2: ...properly in order to provide adequate protection Every installation should be evaluated by a security professional to ensure that all access points and areas are covered Locks and latches on windows and doors must be secure and operate as intended Windows doors walls ceilings and other building materials must be of sufficient strength and construction to provide the level of protection expected A ...

Page 3: ...Panel 6 Programming the System 6 Hardware Reset of Memory to Factory Defaults 7 PC4020 Main Board Specifications_______________________________________ 8 Control Panel 8 Output Voltage 8 Remote Keypad 8 Module Specifications ____________________________________________________ 9 PC4108 Expansion Module 9 PC4116 Expansion Module 9 PC4164 Expansion Module 9 PC4204 High Current Output Module 9 PC4216...

Page 4: ...25 Walk Test 6 Walk Test Code 25 Utility Output 7 or 7 Access Code 25 Installer s Programming Commands 8 Installer s Code 25 At Home Arming 9 Access Code 25 Quick Arm 0 25 Quick Exit 0 When Armed 25 Keypad Zones 25 Access Control Functions _______________________________________________ 26 Reader LED Flash Rates 26 Buzzer Operation 26 How to Setup and Use an Access Card 26 Arming and Disarming Usi...

Page 5: ...in panel processes signal information and communicating with the monitoring station The main panel is capable of supervising 16 zones any of which may be defined for fire or burglary applications and also manages up to eight separate and fully independent partitions assigning zones and their controlling keypads in accordance with installer programming The basic 16 zone capability of the PC4020 can...

Page 6: ...s PC4003C 1 module PC4004C Attack resistant for PC4020 plus 2 modules PC3000 PC4820 Supervised Alarm Output Bell Output 700 mA fused at 5 Amps 12 VDC commercial and 11 6 12 6 VDC residential Steady or Pulsed Output Programmable for 1 of 28 options Event Buffer 3000 events Date and time stamp Event Buffer Viewing any System Master is able to view 2500 events through the keypad including date and ti...

Page 7: ...ill allow the partition setup done without mistakes Locate any zone expansion modules PC4108 or PC4116 required close to groups of zones for easier wiring Decide on the order to enroll the expansion modules The first 16 zones 1 through 16 are on the main panel As each module is enrolled it will be assigned in sequence the next available group of zones If an 8 zone module PC4108 was enrolled first ...

Page 8: ...ote the zone may require to be tripped more depending on the location of the zone On the restoral of the zone for the second time the panel will display a rating of the zones placing with respect to RF strength The Placement Result may be Good Fair or Poor A placement rating of Good means that the zone is placed in a location that has strong RF transmission strength A placement rating of Fair mean...

Page 9: ...ized For example if the microprocessor on the module has been scrambled due to a transient the PC4020 will power down the COMBUS the PC4204 will mimic the PC4020 and cut off its power supply to the module The module will be powered down When the PC4020 returns power to the COMBUS the PC4204 will reconnect its power supply and the power to the module will return Because the module was powered down ...

Page 10: ...dily available Once all modules are enrolled perform a diagnostics check on the panel to determine if any problems are present see Diagnostics Programming the System The PC4020 has the capability to operate as 8 separate alarm systems called Partitions Dividing the panel into Partitions will allow you to control access to specific areas When the PC4020 is first powered up all zones on the main boa...

Page 11: ... light on the keypad If it is on press then 2 to determine the trouble The Trouble Display section in Keypad Functions gives a description of the different trouble conditions Step 5 Instructing the End User Describe system operation to authorized users Provide user with the instruction manual and instruct them to read it to become familiar with the system operation Instruct the user to test the sy...

Page 12: ...Internal clock locked to AC power frequency or optional crystal time base Switched Auxiliary Supply Output Programmable for 1 of 35 options 11 6 12 6 VDC 300 mA maximum Battery 12 volt 4 Ah minimum rechargeable gel cell or sealed lead acid battery Transformer 16 5 VAC 40VA Output Voltage Typically with normal AC on and a fully charged battery the output voltage will be 13 8 VDC With AC off and the...

Page 13: ...es Low COMBUS supervision to the PC4020KT AUX output provides 125mA supply power at 13 8V Provides Lock output supervision to the PC4020 Provides Reader power supervision to the PC4020 PC4108 Expansion Module Up to 128 zones total on system 8 zone expansion module Normally closed loops EOL resistor Double EOL resistor support 4 wire QUAD hook up to COMBUS Nominal current draw of 25 mA Provides Tam...

Page 14: ... OF LINE RESISTOR ANY Z TERMINAL ANY COM TERMINAL TYPICAL ZONE CIRCUITS TELEPHONE CONNECTION GROUND CONNECTION 120 V 40 VA TRANSFORMER 16 18 V 40 VA DO NOT CONNECT TO RECEPTACLE Nut Washer Cabinet Bolt Ground Rod TO GROUND CONNECTION INCOMING LINE FROM TELEPHONE COMPANY OUT TO TELEPHONE EQUIPMENT ON PREMISES GRY BRN RED GRN Recommended use with Double EOL Resistors 5600Ω End Of Line resistor colou...

Page 15: ...11 Module Hookup Diagram ...

Page 16: ...WIRING IS REQUIRED FOR RESIDENTIAL FIRE ALARM SYSTEMS SW AUX PROGRAMMED FOR SENSOR RESET TO ANY COM TERMINAL TO ANY ZONE Z TERMINAL TO ZONE Z TERMINAL PROGRAMMED FOR FIRE TO ANY COM TERMINAL BELL LOOP 700 mA MAX 4 WIRE SMOKE DETECTOR POWER 11 VDC 400 mA MAX Bell Current mA 50 2750 838 1375 419 690 210 460 140 345 105 275 83 230 70 195 59 1740 530 870 265 435 132 290 88 215 65 170 52 140 43 125 38 ...

Page 17: ...e with controlled devices TERMINAL CONNECTIONS COMBUS Terminals RED BLK YEL and GRN Connect the red wire of the COMBUS to the RED terminal the black wire to the BLK terminal the yellow wire to the YEL terminal and the green wire to the GRN terminal The COMBUS is wired in the same manner on all modules The COMBUS is used by the main panel to communicate with and supply power to the modules The COMB...

Page 18: ...s and jacks meet the dimension tolerance and metallic plating requirements of 47 C F R Part 68 Subpart F TIP Green wire Incoming line from RNG Red wire telephone company T 1 Brown wire Outgoing line to R 1 Grey wire house telephone s Battery Connections Do not connect the battery or the transformer until the wiring is complete Connect the red battery lead to the positive battery terminal and the b...

Page 19: ... An access code is a 4 or 6 digit optional number which will permit access to the system i e Arm Disarm control Installer s Programming etc User access codes are programmed in the User Programming section 5 The default access code is 1234 for 4 digit option and 123456 for 6 digit option See User Programming Commands for details on programming access codes Global Keypads What is a Global Keypad A g...

Page 20: ...on Label Pressing the right arrow key displays the message SELECT 1 FOR OPTIONS If the selected partition is armed the LCD will prompt with the message SELECT 0 DISARM PARTITION If option 0 is selected the panel will disarm the partition and display the message SYSTEM DISARMED NO ALARM MEMORY for 2 seconds Then the display will return to SELECT 1 Partition Label If the user chooses 1 For Option th...

Page 21: ...r communicator program information The installer s program code may be changed by the installer Arming Close all protected doors and windows and stop movement in areas covered by motion detectors The Enter Code To Arm System message should be on the LCD display The system cannot be armed unless the Enter Code to Arm System or Secure System or Enter Code message is displayed If Double EOL resistors...

Page 22: ... displayed with the partition status at the right corner of the LCD To disarm the partition being viewed simply press or use the hot key 0 If 1 For Options is selected the user will be prompted with the message KEYPAD LOANED TO Partition Label on the LCD display From here the user is capable of performing all functions e g 7 Door Strike and arm the panel using the conventional methods Once the key...

Page 23: ...ns If one of these conditions occurs the keypad TROUBLE indicator will light and the audible indication will sound two short beeps every 10 seconds When the key is pressed the audible indication will stop but the trouble indicator light will remain ON until the trouble is cleared Trouble conditions can also be transmitted to the monitoring station Press the then 2 keys to display the types of trou...

Page 24: ...unicating COMBUS Low Pwr Modules are not getting enough voltage from the COMBUS Check for proper connection of COMBUS or the COMBUS needs to be repowered See 4204 modules and the 4204 PGM COMBUS power option for supplying voltage to the COMBUS See Diagnostics in the Programming Manual to determine which module has low voltage Internal Fault A problem has occurred with the COMBUS microprocessors If...

Page 25: ...low battery condition To view which zone has the trouble press the key while viewing the trouble condition The zone s with the trouble condition will be displayed in numerical order on the display A keypad trouble is generated when the system is disarmed and a visual Zn Low Batt Fault trouble and trouble reporting code will be transmitted Automation Fault This trouble condition will occur well the...

Page 26: ...hedule window is active unless a user with a Privileged card grants the user access to the system When the Second Card Schedule is not active out of window the user will be able to access the assigned door s on the system Programming Additional Access Codes Using a System Master or a Supervisory Code Press then 5 to enter the User Programming Commands the keypad will display the message Enter Your...

Page 27: ...ode will not operate on any partition 7 To Exit the menu press the key 2 User Name Search 1 This option will allow selection of the user to be programmed by searching using the user name To do this enter the first letter of the user s name eg for John enter the letter J press the 4 key once and press either arrow key or This will find all users whose names begin with the selected letter upper or l...

Page 28: ...eypad When this function is selected the Keypad Setup menu will appear on the keypad Bright Control adjusts the level of backlighting on the LCD display and the backlighting on the keys Contrast Control adjusts the contrast of the lettering on the LCD display Use the keys to toggle through the eight different settings and press to select the level of preference Note To adjust the keypad brightness...

Page 29: ...nd P keys will activate for all active partitions any valid access code from any partition may silence the alarm Note See KEYPAD TOG OPT in the Programming Guide for changing keypad zones options The sixth message is Zone Tamper It will be displayed if the zone is opened while using Double EOL resistors See Event Messages in the Programming Guide Note The Zone Fault and Zone Tamper event messages ...

Page 30: ...r each door to allow access at only specific times of the day If the user is to have arming disarming abilities the user must be assigned to a partition and the installer must assign the door s arm disarm mask to the same partition s To gain access to a locked access control door first swipe the card in the method indicated by the access card reader installation manual When the LED on the reader c...

Page 31: ... the access code names See ZONE LABEL in the Programming Manual for programming zone labels The printout will then be as Sample 3 The PC4400 sends events to the printer as they occur If the printer is off line or disconnected the PC4020 keeps new events in memory until they are ready to be printed When the printer is brought back on line the PC4400 will send the new events to the printer If 450 ne...

Page 32: ... to the tip and ring terminals on the panel A DTS 1 must be connected to the lines and in the local mode Program the downloading access code and panel I D code Program a zone for Forced Answer See Zone Type in the Programming Guide This zone is only meant to be temporary to initiate downloading It can later be changed back to the required zone type Make sure the access code and panel I D code are ...

Page 33: ...99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 2...

Page 34: ...er 51 1 52 2 53 3 54 4 55 5 56 6 57 7 58 8 59 9 60 10 61 11 62 12 63 13 64 14 65 15 66 16 Indicated PC4700 Number Fire Module 67 1 Indicated VPM 2 Number Voice Prompting Module 68 1 Indicated PC4820 Number Access Control 69 1 70 2 71 3 72 4 73 5 74 6 75 7 76 8 77 9 78 10 79 11 80 12 81 13 82 14 83 15 84 16 E Communication error T Tamper open LV Low voltage to module Indicated For Future Use Number...

Page 35: ......

Page 36: ... 1997 2002 Digital Security Controls Ltd Toronto Canada www dsc com Technical Support 1 800 387 3630 Printed in Canada 29002586 R0 ...

Reviews: