3G4000 Wiring Diagram
4
Figure 1 - Wiring Diagram
Supervision
Relay
Optional
use of PGM
output (See
Programming)
WARNING:
Incorrect connections may result in PTC failure or improper operation. Inspect wiring and ensure connections are correct before
turning on.
All circuits are classified for UL
installations as Power Limited/Class II Power Limited. Do not route any wiring over circuit
boards. Maintain at least 1” (25.4mm) separation.
A
minimum 1/4” (6.4mm) separation must be maintained at all points between Power Limited wiring and all other Non-Power Limited w
iring. Route wires as indicated in the diagram.
NOTE: For ULC Commercial Burglary Installation requirements please refer to Figure 5 and to the ULC Installation Guide P/N 2900
2157.
Telephone Line
Connection
RJ-45
For use in dry indoor ordinary locations only
. For installation refer to NFP
A70, 72.
Examples of control units/Subscribers Unit or power supplies compatible models:
DSC PC1864, HS2128, PC5204, HSM2204.
Electrical Ratings: 13.8 V
DC
/ 700 mA
use
ADP1320-NAU/NA
(US/CDN) and
Battery: 7.2V/2.2Ah
Electrical ratings: 9-14V
DC
/500mA
use listed control panel or power supply
Alarm Control Panel with
Dialler Interface
(Supports Contact ID
format)
BA
TTER
Y
Sealed
Rechargeable
7.2V / 2.2Ah
RM1-UL
Installations
RM1C-ULC Installations
Connect relay contacts to a zone input on the alarm control
panel for 3G4000 troubles supervision (24hr-type zone)
T I P
R I N G
Panel
Aux Power or External Power Supply
AUX
Output of the control panel (which can power the
communicator) shall be rated LPS (power limited). Use only
power supplies that have
AUX output isolated from EGND
T
ypical battery charge: 30-50 mA
Recommended Model: NiMH, Rated 7.2V
, 2.2Ah
Use only: Model 6PH-H-AA2200-S-D22 from Great Power
.
3G4000
TIP
RING
T1
R1
Z1
PGM1
Z2
PGM2
DC IN
+
-
1
2
3
4
5
6
7
9
8
10
WARNING!
HIGH VOL
T
AGE.
DISCONNECT DC
POWER AND
TELEPHONE LINES
PRIOR T
O SER
VICING.
Incorrect connections
may result in failure
or improper operation.
}
Inputs to be connected
to dry contact outputs
from alarm control panel
(Use No. 26
A
WG
wires for the
connection to PSTN)
+12V
1K5
For UL
Installations, the system shall be installed in accordance with chapter 2 of the
ANSI/NFP
A
72 and
ANSI/NFP
A70. Recommend
ed loca-
tions and wiring methods shall be in accordance with the National Electrical Code,
ANSI/NFP
A
70, the Standard for Installation
and Classifica-
tion of Burglar and Holdup
Alarm Systems, UL
681, and the Standard for Central-Station
Alarm Services, UL
827.
For ULC Installations, the recommended locations and wiring methods shall be in a
ccordance with CSA
C22.1, Canadian Electrical
Code, Part
I, Safety Standard for Electrical Installations; CAN/ULC-S302, Installation and Classification of Burglar
Alarm Systems for Fin
ancial and Com-
mercial Premises, Safes and V
aults; and CAN/ULC-S301, Standard for Central and Monitoring Station Burglar
Alarm Systems and th
e Stan-
dard for the Installation of Residential Fire W
arning Systems, CAN/ULC-S540. Do not install the equipment in places where the s
ignal strength
does not meet the minium recomended signal strength level. Do not run zone inputs
and
T1/R1 wiring along
AC wires or other circ
uits with high
frequency signals in order to reduce possibility of interference and false alarms.