Relay setting 

 

Relays electrical connection 

AN401Plus can have up to 2 internal alarm level cards installed, with 2 
relays each, on slots A and B  (with only one card It will be applied in 
slot B): see figure for electrical connections. 
 

Relays electrical specifications 

- Maximum voltage : 30 Vdc. 
- Maximum current : 2 A. 
- Maximum power : 1W. 
- Switching delay time: 2 mS. 

 

Alarm levels menu

 

 

SET parameter

 

Parameter

 

Description

 

Default

 

Possible values

 

 

Working MODE

 

Function

 

LEV0 

Level 0 switching value 

1000 

±99999 

 

Relè disabled  

HIS0 

Level 0 hysteresis 

from 0 to 50 

 

GROSS showing on display. 

SET0 

Level 0 configuration 

See SET parameter 

 

NET showing on display. 

LEV1 

Level 1 switching value 

1000 

±99999 

 

Positive peak value 

HIS1 

Level 1 hysteresis 

from 0 to 50 

 

Negative peak value 

SET1 

Level 1 configuration 

See SET parameter 

 

 

 

LEV2 

Level 2 switching value 

1000 

±99999 

 

 

 

HIS2 

Level 2 hysteresis 

from 0 to 50 

 

 

 

SET2 

Level 2 configuration 

See SET parameter 

 

 

 

LEV3 

Level 3 switching value 

1000 

±99999 

 

 

 

HIS3 

Level 3 hysteresis 

from 0 to 50 

 

 

 

SET3 

Level 3 configuration 

See SET parameter 

 

 

 

Alarm level setting 

1.

 

Press 

during normal use of AN401Plus. 

2.

 

Display shows 

LEV0

: press 

to change value. 

3.

 

Display shows default value 

1000

: press

 

to store the desired value. To increase or decrease the value press 

 

or

; to increase It 

fastly press, at the same time, 

 

and 

 

E

 or 

and

 

E

 to decrease It fastly . 

4.

 

Display shows 

LEV0

: press

 

5.

 

Display shows 

his0

: press

 

to change value. 

6.

 

Display shows default value 

0

    :  press

 

to memorize desired hysteresis value (reduces noise effect on levels).To increase or 

decrease the value press 

 

or

; to increase It quickly press 

 

and 

 

E

, at the same time, or 

and

 

E

 to decrease It quickly. 

7.

 

Display shows 

his0

: press

 

.

 

8.

 

Display shows 

SET0

: press

 

to change value. 

9.

 

Display shows default value 

0

: press

 

to store the desired value. To increase or decrease the value press 

 

or

; to increase It 

fastly press, at the same time, 

 

and 

 

E

 or 

and

 

E

 to decrease It fastly . 

10.

 

Repeat point 2 to 7 to set alarm levels for the the other relays. 

11.

 

Press 

C:

 to exit from alarm level setting menu. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 