background image

 

11

 
 

7.4.4 Operative 

parameters 

 

Parameter 

Description 

Operative range 

Dropsa setting 

Timer* 

A timer defines lube duration 

00m01s ÷ 4m59s

 

PS

 

Lube starts when system is in 
pressure (Pressure is 
monitored by a pressure-
switch) 

LUBE Type 
 

SEP

 

A proximity sensor detects 
the changes of position of the 
piston: after three changes a 
lube cycle is completed 

10s ÷ 99 min. 

00m:10s 

Timer* 

A timer defines standby 
duration (system idle) 

01m00s ÷ 999h59m59s 

06m:00s 

Pulse 

A pulse register defines 
standby duration (system idle)

1i ÷ 9,999,999i 

100i 

STANDBY 
Type  
 

Both 

Standby duration (system 
idle) is defined by both 
standby timers (timer and 
pulse), whichever occurs first 

See Standby  

Timer and pulse 

 

06m:00s 

100i 

DELAY TIME  
(FOR PS ONLY) 

A timer defines the duration of 
PUMP ON (time lag for pump 
OFF) once the system goes in 
pressure 

01s ÷ 99 min. 

00m:02s 

LUBE Cycles 

Number of lube cycles to be 
carried out  by the system 

01÷ 999 

PRELUBE cycles 

Number of prelube cycles, 
which will be carried out 
before the lube cycles

 

1÷ 999

 

WAIT Time 

A timer  defines the duration 
of a 

pause time

 between each 

lube process.

 

ONLY  for ‘LUBE type: SEP’:  
Set  00m00s for continuous 
service

 

01s ÷ 16m39s 

00m:05s 

START IN LUBRIC. 

START MODE 

It allows to choose how to 
start the working session 

START IN STANDBY 

START IN LUBRIC.

Norm. Open 

Alarm 

It allows to choose the type of 
alarm electric contact 

Norm. Close 

Norm. Close 

Date & Time 

It allows to enable/disable 
Date & time display and setup

Enabled/Disabled Enabled 

Day 

It allows to set the day 

1-31 

Month 

It allows to set the month

 

1-12 1 

Year 

It allows to set the year

 

2000÷2099 2004 

Hour 

It allows to set the hour

 

0-23 0 

Minute 

It allows to set the minutes

 

00-59 00 

*Default setting: Lube type: Timer; Standby Type: Timer; Date & Time: Enabled 
 
NOTICE: When Date and Time are enabled, in order to avoid controller malfunctioning, it is 
recommended to set 

day

month 

and 

year

 in accordance with the calendar. 

 
 
 

7.5 

 

I-R communication 

Controller VIP2004

 is provided with an I-R port for infra-red communication via special I-R device and Dropsa 

software to be installed on your PC. This innovative system will allow you to 

remotely

 manage (1÷1.5 m – 39 ÷ 

60 in.-) two important operations: 

Lube status reading-> 

reading of the machine data on your PC: lube parameters, date, time and 

logs;

 

Machine programming 

-> setup of the machine data from your PC: lube parameters, date and time.

 

The 

I-R

 

communication system (Dropsa software included)

 is furnishable by Dropsa on demand.

 

 

 

Summary of Contents for SMART2

Page 1: ...HE MACHINE 7 INSTRUCTIONS FOR USE 8 TROUBLESHOOTING 9 MAINTENANCE PROCEDURE 10 DISPOSAL 11 ORDERING INFORMATION 12 DIMENSIONS 13 HANDLING AND TRANSPORTATION 14 OPERATING HAZARDS 15 PRECAUTIONS 16 WARR...

Page 2: ...tion cycles lubrication will be described in paragraph 2 1 2 necessary to vent air from the pump and check lubrication functions Prelube takes place on POWER ON on RESET Any time new parameters are se...

Page 3: ...66 gals By pass Calibration 25 bar 367 5 psi Pressure Switch calibration 18 bar 264 6 psi Insulation Class B Rotation direction clockwise Revolutions min 2900 3500 2900 Max working time in continuous...

Page 4: ...serial On the front panel there are Push button for manual control MANUAL LED indicator for PUMP ON 5 1 AUTOMATIC SMART2 VIP2004 Controller located under the cover of automatic SMART2 allows pump tot...

Page 5: ...d the unit Do not install the unit in aggressive or explosive inflammable environments or on vibrating surfaces To install the pump use only the supplied bracket provided with two holes for 6 mm 0 2 i...

Page 6: ...n terminal M2 Furthermore it is also shown how to change the type of connection indipendent or serial for the pressure switch and electric level contact by acting on the jumper located on the electron...

Page 7: ...each time the bridge is removed and then put back in place In order to make a complete reset of the machine remove the bridge and switch off the machine 6 4 4 PRECAUTIONS TO BE TAKEN DURING CONNECTING...

Page 8: ...ubricant and refill the reservoir by means of the oil refill plug provided with a filter Do not pour lubricant directly into the reservoir without using this oil refill plug 7 3 2 Machine start up In...

Page 9: ...UBE X 2 TIMER 00m05s STOP STANDBY 01m00s setup start PRELUBE X 3 TIMER 00m05s STOP PRELUBE will be carried out only when prelube cycles are set PRELUBE 0 Whether prelube has been completely carried ou...

Page 10: ...NLY for PS To modify DELAY Time for pump OFF To modify LUBE Cycle To modify WAIT Time between two or more lube cycles Note this parameter is displayed only if Lube or Prelube 1 To select START mode sy...

Page 11: ...continuous service 01s 16m39s 00m 05s START IN LUBRIC START MODE It allows to choose how to start the working session START IN STANDBY START IN LUBRIC Norm Open Alarm It allows to choose the type of a...

Page 12: ...nds ALARM 01 TIMER FAULT Internal process error during lube by timer ALARM 02 PX VENT FAILED At the beginning of lube by PS it was detected that the system has not vented air ALARM 04 PS PRESSURE ALAR...

Page 13: ...ure that the identification label and all the other relative documents are also destroyed 11 ORDERING INFORMATION 11 1 MANUAL SMART2 11 2 AUTOMATIC SMART2 PART N DESCRIPTION 3600240 SMART2 ELECTRO PUM...

Page 14: ...manual 3600904 Motor unit for SMART2 110V 60Hz automatic and manual 3600905 Motor unit for SMART2 220V 50Hz automatic and manual 6770033 Transparent reservoir 3 litres 0 66 gals 3292053 Manometer 60...

Page 15: ...any intervention check the absence of residual pressure in any branch of the lubricant circuit as it may cause oil sprays when disassembling components or fittings Noise Pump does not produce excessi...

Page 16: ...paid receipt of subject product to an authorized Dropsa Sales Service location we will then either repair or replace such product s at out option and if determined to be a warranted defect we will per...

Page 17: ...red in conformance with the EUROPEAN COMMUNITY DIRECTIVE relating to machines 98 37 EC 91 368 EEC low voltage BT 73 23 EEC Has been manufactured in conformance with the following technical harmonised...

Page 18: ...el 55 011 5631 0007 Fax 55 011 5631 9408 E mail salesbr dropsa com Dropsa S p A Via B Croce 1 20090 Vimodrone MI Italy Tel 39 02 250 79 1 Fax 39 02 250 79 767 E mail sales dropsa it Export E mail vend...

Reviews: