speedy
Option 25 EIP/PCCC Server
Supports EIP/PCCC Typed-Write and Typed-Read functions.
See Appendix B of
savvy
User Manual for information,
examples and
drive.web
to PLC parameter mapping.
Supports up to
two simultaneous clients.
ModbusRTU Master
& bus-share drive interface
Adding network devices may affect dedicated drive’s serial link performance.
Modbus Function Codes
FC
01-06
and
16
are supported. Also
Yaskawa Holding Register function.
Note
: Modbus address 1 is the dedicated drive’s address for
dw222
,
dw223
and
dw226
.
dw225
’s dedicated drive is
address 0x1F or 31. Bus-sharing Modbus servers must use
different addresses.
Comms Port
function block
Comms Speed
Read-only for drive-dedicated
speedy
’s.
dw220
, choose standard
speeds are enter baud rate 0.1 to 500Kbps.
Comms Configuration
Read-only in
dedicated
speedy
’s.
Character frame is
1-8-Parity-Stop
:
Parity
is
N
None,
O
Odd,
E
Even,
S
Space(0) or
M
Mark(1).
Number of
Stop
bits;
1, 1.5
or
2
.
Minimum Comms Silence.
Idle on-the-wire time before a new
request is sent. Some devices require longer than minimum 3.5
characters. Longer times decrease comms efficiency.
Bandwidth
. Drive-dedicated models only. The portion of the
bandwidth allocated for all
Modbus Data
blocks.
Actual Polling Period.
Read-Only. Time required to poll all
parameters in all Modbus Data blocks with that priority.
Period is directly affected by number of parameters, silence
times and any errors or timeouts.
Comms Timeout.
10 to 30000ms waits for a reply.
Status
indicates
Timeout
if no reply is received.
drive.web automation
speedy
HG503206beta2
www.driveweb.com
Page 16/20