65
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem
Possible cause
Action
22
23
24
25
Ignitor No. fault
Blower No. fault
Slave No. fault
Control does not
energize.
Broken ignitor
Gas valve/ignitor/
sensing electrode is
out of sequence.
The blower is
incorrectly wired or
the blower failed to
start.
LonTalk
®
communications cable
is not connected
between boards.
Slave board does not
have power or has
incorrect power.
Nonexistent supply
voltage to unit
Nonexistent control
voltage
Heater over-
temperature thermostat
open
Verify that ignitor glows.
Verify wire connections to these
components.
Check for proper blower wiring.
Connect LonTalk communications
cable.
Verify power wiring on slave board.
Check main line fuse.
Check main line safety switch.
Check heater fuses.
Check for proper supply.
Verify proper transformer voltage
characteristics.
Verify proper wiring of transformer.
Check for control circuit voltage, 24
VAC. If voltage is not present, check
transformer circuit breaker. Reset if
needed.
Reset manual switch located above
heater or humidifier cover.
More on next page ...