![DriSteem Vapor-Logic Installation And Operation Manual Download Page 58](http://html1.mh-extra.com/html/dristeem/vapor-logic/vapor-logic_installation-and-operation-manual_2531533058.webp)
54
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Status LED
OPERATION
Table 54-1:
LED indicators
LED Indicator
First Blink
Second Blink
Third Blink
Faults
Communications status
Demand/call for humidification
Green
Auto mode: no faults
Keypad/display is attached and
working
Humidification demand is present
Yellow
Auto mode: active message
preventing unit from running
—
—
Red
Auto mode: active fault preventing
unit from running
Keypad/display is not
communicating with controller
—
Blue
Standby or test mode: unit will not
run
—
No humidification demand present