To create a backup file:
1 . Insert a USB flash drive into the USB port on the Vapor-logic board .
2 . Go to Settings/USB backup-restore/Back up settings
3 . Select Yes . The display will prompt you when backup is complete .
To restore from a backup file:
1 . Insert a USB flash drive with that humidifier’s backup file into the USB port
on the Vapor-logic board .
2 . Go to Settings/USB backup-restore/Restore settings .
3 . Select Yes . Note that the serial number of the humidifier and backup file
must match to complete the restore process .
DOWNLOADING FIRMWARE UPDATES
The Vapor-logic controller and the touchscreen display firmware can be field
upgraded to the latest firmware version via the USB port on each device .
Firmware updates are available at no charge on the DriSteem website . One
download from the DriSteem web site will give you all files needed to update
both Vapor-logic and the touchscreen display .
To update your Vapor-logic controller and/or touchscreen display to the latest
firmware version, perform the following procedure:
1 . Navigate to www .dristeem .com .
2 . Go to
Support & Literature
on the site navigation menu .
3 . Select
Technical Support
.
4 . Click on
firmware updates
.
5 . Navigate to
Vapor-logic6
and click version download link .
6 . Plug a reliable USB flash drive into a USB port on your computer, and
prepare the flash drive as follows:
a) Move or delete all files from the drive .
b) Make sure it has at least 16 MB of free space .
c) Make sure it is not partitioned into multiple drives .
7 . Perform the procedure in Table 62-1 .
8 . Repeat the procedure in Table 62-1 to get the Vapor-logic6 touchscreen
display update files . They can be placed on the same USB stick .
Firmware updates
OPERATION