30
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
INSTALLATION
Step 2 – Setup
Table 30-1:
Settings menu (continued)
Menu item
Default value
Minimum
value
Maximum
value
Units
Notes
Fan Dispersion
Fan Type
--
--
--
--
Space Distribution
Unit
--
--
--
--
Fan Off Delay
5
1
30
Minutes
Area-Type Fan
--
--
--
--
Auxiliary Temperature Sensor
Purpose
Not Used
--
--
--
Temperature
Compensation
--
--
--
--
Sensor Offset
0
-20
20
°F
0
-11
11
°C
Temperature
Monitoring
--
--
--
--
Sensor Offset
0
-20
20
°F
0
-11
11
°C
Not Used
--
--
--
--
Programmable Outputs
Dry Contact 1 or 2
--
--
--
--
CAUTION
Programmable dry contact maximum current
Programmable dry contact (P12 or P16) is rated for 125 VAC,
3 AMP or 30 VDC, 3 AMP maximum . Exceeding this maximum
rating can cause the dry contact (relay) component or the Vapor-
logic board to fail .
Contact Behavior
Normally
open
Normally
open
Normally
closed
--
Contact action on event
Contact Purpose
Default Alerts
--
--
--
Default Alerts
View Default
Alerts
--
--
--
--
A dry contact activates whenever there is an alert,
which does not auto-clear .
Selected Alerts
Alert selection
--
--
--
--
A dry contact activates whenever there are alerts selected from
the alert selection list .
Alert on Low RH
--
--
--
--
Alert below RH
50
0
100
--
Contact toggles whenever the space humidity falls below the low
RH setting . Adjust the contact behavior to either open or close
when the space RH gets low . To use this feature the control input
signal type must be an RH transmitter .
Steam Yes/No
--
--
--
--
A dry contact activates when the tank temperature reaches
boiling
Heat On/Off
--
--
--
--
A dry contact activates when the humidifier is heating .
Not Used
--
--
--
--