1
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Unpacking High-Effi ciency Tubes
NOTE: If you have an Ultra-sorb without High-effi ciency dispersion tubes (non-
insulated tubes), please skip to the next page.
UNPACKING
• Remove the dispersion assembly from the shipping container; be careful not
to damage the PVDF insulating material on the dispersion tubes.
• Some dispersion panels are shipped unassembled. Do not lay High-
Effi ciency Tubes across or under anything that could compress or damage
the insulating material. Compressed insulating material has a reduced
R-value.
• Before start-up, remove the clear poly fi lm covering the insulation by tearing
it along the perforation.
Do not use a knife or sharp object to remove the
poly fi lm.
High-efficiency tube option
Dispersion assemblies with the High-Effi ciency
Tube option are designed to produce
signifi cantly less dispersion-generated
condensate and airstream heat gain, which
reduces wasted energy by up to 85%.
CAUTION
Remove clear poly fi lm; do not remove white PVDF insulation.
High-effi ciency tubes are sleeved in clear poly fi lm for
protection during, shipping, and installation. Leave the clear
poly fi lm on until installation is complete.
Remove and discard the clear poly fi lm before start-up by
tearing it along the perforations.
Do not remove the white
PVDF insulation.
•
Keep fl ame away from the insulation to avoid damage.
•
PVDF is resistant to UV light. UV-C light from
germicidal lamps will not cause the insulating
material to degrade.
•
Do not tighten mounting clamps or fasteners to any part of the dispersion tube.
UNPACKING HIGH-EFFICIENCY TUBES