26
ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Troubleshooting
MAINTENANCE
Table 25-1:
Ultra-sorb Model MP troubleshooting
Problem
Possible cause
Action
Control system
malfunctioning
• Incorrect control voltage
• Replace transformer.
• Incorrect control signal
• Replace components.
• Improper wiring connections
• Rewire.
• Incorrect humidity sensor
• Replace.
• Humidity controller out of calibration
• Recalibrate.
Air cannot absorb
steam quantity being
discharged
• Humidifi er operates when blower is off
• Provide interlock.
• Valve is hunting
• See above.
• Air temperature in duct too low for steam
quantity being emitted
• Raise duct air temperature.
Humidifi er is noisy
• Steam pressure too high
• Reduce pressure.
Continued